29
APPENDIX A - USER INTERFACE MENUS (CON’T)
System Settings Menu
BACview Menu
POINT NAME
BACnet Object
RANGE
DEFAULT
Field Assistant Menu
STANDBY
RTU Open
BACview Only
System Mode
run_status
1=Off
2=Fan Only
3=Economizer
4=Cooling
5=Heating
6=Dehumidification
7=Test
8=Shutdown
9=Unocc Free Cooling (NT-
FC)
10=Fire Shutdown
11=IAQ Override
12=Pre- OCC Purge
Space Temperature
space_temp
xxx ° F
Press any key to activate
LOGIN/LOGOUT
Admin or User Password
****
User: 0000 Admin: 1111
HOME
Select function below
HOME>
SYSTEM SETTINGS>
SYSTEM SETTINGS
BACnet
BACnet Device Instance:
xxxxxxx
1610100
Base BACnet Device ID:
xxxxxxx
1610100
Autogenerate Device ID?
Y/N
Y
Keypad
Keypad Configuration
Inactivity Timeout:
1- 255 minutes
10
BACnet Write Priority:
0- 16
0
UserPw
View/Set User
Password:
****
0000
NETWORK
NETWORK
Max Masters
this_device/64
1- 127
127
Max Info Frames
this_device/63
1- 999
10
APDU Timeout (ms)
this_device/11
1- 10000
3000
APDU Retries
this_device/73
1- 10
3
MS/TP Baud Rate
this_device/4161(1)
9600- 76800
76800
ClockSet
Set Current Time/Date (24 hr clock)
Time (hh:mm:ss):
Date (dd- mmm- yy):
DST
DST
Start Time:
Amount:
Entry #
Beg (mm- dd- yy)
End (mm- dd- yy)
TimeMstr
BACnet Time Master
Time Sync Mode
No Broadcast
Local Broadcast
Global Broadcast
No Broadcast
Time Sync Interval
1- 9999 minutes
5
TS
-
5580
-
01