APPENDIX A - USER INTERFACE MENUS (CON’T)
Configuration Menus (con’t)
BACview Menu
POINT NAME
BACnet Object
RANGE
DEFAULT
Field Assistant Menu
SETPOINT
HOME>CONFIG>
SETPOINT
Occupied Heating Setpoint
occupied_heat_setpoint
40- 90 ° F
70
Properties>Equipment>
Configuration>Setpoints
Occupied Cooling Setpoint
occupied_cool_setpoint
55- 99 ° F
76
Unoccupied Heating Setpoint
unoccupied_heat_set-
point
40- 90 ° F
55
Unoccupied Cooling Setpoint
unoccupied_cool_set-
point
45- 99 ° F
90
Effective Heat Setpoint
effective_heat_setpoint
0- 120 ° F
Effective Cool Setpoint
effective_cool_setpoint
0- 120 ° F
Optimal Start (hrs)
optm_start
0- 4 hr
4
Optimal Start Type
start_type
1=None
2=Learning Adaptive
3=Temp Compensated
Temperature Compensated
Heat Start K factor (min/deg)
h_kfactor
0- 99
15
Cool Start K factor (min/deg)
c_kfactor
0- 99
15
DCV Max Ctrl Setpoint
iaq_stpt_max
0- 9999 ppm
650
Power Exhaust Setpoint
pexh_stpt
20- 90 %Open
50
Occ Relative Humidity Setpoint
occ_dehum_stpt
0- unocc setpoint %rh
60
Unocc Relative Humidity Setpoint
unocc_dehum_stpt
30- 100 %rh
95
HOME>CONFIG>
Sched
Schedule
(BACview only)
Weekly schedule
MON- SUN
none
Exceptions
none
ALARM CONFIGURATION
HOME>CONFIG>
ALARMS
SPACE TEMPERATURE ALARM
Properties>Equipment>
Configuration>
Alarm Configuration
Occupied Alarm Hysteresis
occ_spt_alrm_hyst
0- 20° F
5
Alarm Delay (min/deg)
spt_alrm_delay
0- 60 minutes
10
Unoccupied Low SPT Alarm Limit
uno_spt_alrm_lo_lmt
35- 90 ° F
45
Unoccupied High SPT Alarm Limit
uno_spt_alrm_hi_lmt
45- 100 ° F
95
SUPPLY AIR TEMPERATURE ALARM
Low SAT Alarm Limit
sat_lo_alrm_lim
15- 90 ° F
38
High SAT Alarm Limit
sat_hi_alrm_lim
90- 175 ° F
160
SPACE HUMIDITY ALARM
Occupied High RH Alarm Limit
(%RH)
sprh_hi_alrm_lim
0- 100%rh
70%rh
Alarm Delay (min/%RH)
sprh_delay
0- 30 min
5 min
Unoccupied High RH Alarm Limit
(%RH)
unocc_sprh_lmt
0- 100%rh
100%rh
Low RH Alarm Limit (%RH)
sprh_lo_alrm_lim
0- 100%rh
30%rh
IAQ / VENTILATION ALARM
Occ High CO2 Alarm Limit (ppm)
iaq_occ_hi_lmt
0- 9999 ppm
1200