13
X-VA-MT3809G-MT3810G-eng/541B182AAG/A/2022-10
Brooks Instrument
Installation Manual MT3809G & MT3810G
Section 1 Introduction
F
OUNDATION
Fieldbus Transmitter, with Alarms and Pulse Output
Design Features
• F
OUNDATION
TM
Fieldbus digital communication network interface
• Ease of wiring and installation with a single 2-wire bus connection
• Powered over 2-wire F
OUNDATION
TM
Fieldbus connection
)OH[LEOHPL[ PDWFKXQLWVRIPHDVXUHIRUÀRZUDWHVWRWDOV
temperatures, densities, etc.
7ZRÀRZWRWDOL]HUV5HVHWWDEOHDQGLQYHQWRU\WRWDOL]DWLRQ
8VHUFRQ¿JXUDEOHVFDODEOHSXOVHRXWSXWIRUYDULRXVHQJLQHHULQJXQLWV
+LDQG/RÀRZDODUPRXWSXW
Description
The F
OUNDATION
TM
Fieldbus transmitter is a compact microprocessor device
designed to interface directly with the Model MT3809.
The transmitter communicates over the 2-wire network per the
international F
OUNDATION
TM
Fieldbus standard for access to numerous
YDULDEOHVVXFKDVÀRZUDWHWRWDOL]DWLRQFDOLEUDWLRQIDFWRUVDQGKLJKORZ
alarm parameters.
7DEOH)
OUNDATION
)LHOGEXV7UDQVPLWWHU'HVFULSWLRQ7DEOH
Power
supply
voltage
9
Ͳ
32Vdc
Power
supply
protection
Protected
against
reverse
polarity
Current
consumption
12
mA
Entire
transmitter
is
powered
from
2
Ͳ
wire
bus
Hi
Ͳ
and
Lo
Ͳ
alarm
outputs
Open
collector
alarm
output
Optically
isolated
outputs
assignable
to
alarms.
•
Max.
off
Ͳ
state
voltage:
30
Vdc
•
Max.
off
Ͳ
state
current:
0,05
mA
•
Max.
on
Ͳ
state
voltage:
1.2
Vdc
•
Max.
on
Ͳ
state
current:
20
mA
Pulse
Output
Optically
isolated.
Scalable
to
a
variety
of
engineering
unit
systems
(pulses
per
liter,
gallons,
etc.).
•
Range:
1
Hz
to
1
kHz
•
Max.
off
Ͳ
state
voltage:
30
Vdc
•
Max.
off
Ͳ
state
current:
0.05
mA
•
Max.
on
Ͳ
state
voltage:
1.2
Vdc
•
Max.
on
Ͳ
state
current:
20
mA
Temperature
Specification
See
Temperature
Cut
Ͳ
off
Table
Electrical
Connector
M20
x
1,5
according
to
ISO
(1/2"
NPT,
3/4”
NPT
(F)
or
cable
gland
optional)
•
Brass/Nickel
plated
cable
gland
cable
diameter
range
8
Ͳ
11
mm
(Aluminum
housing)
•
Stainless
steel
cable
gland
cable
diameter
range
7
Ͳ
10.5
mm
(SS
housing)
Linearity
Less
than
1%
Temperature
Influence
Less
than
0.04%
per
°C
Voltage
influence
Less
than
0.002%
/
Vdc
FOUNDATION
Fieldbus
Revision
ITK6