19
X-VA-MT3809G-MT3810G-eng/541B182AAG/A/2022-10
Brooks Instrument
Installation Manual MT3809G & MT3810G
Section 1 Introduction
7DEOH3URFHVVDQG$PELHQW7HPSHUDWXUH/LPLWV'RFXPHQW=FRQWLQXHG
T6
T6
T5
T4
T3
T2
Approval
type
Housing type
Ambient
Temperature (°C)
Without
Inductive
Alarm
With Inductive
Alarm
With or without
Inductive
Alarm
With or without
Inductive
Alarm
With or without
Inductive
Alarm
With or without
Inductive
Alarm
-40 to 40
85
85
100
126
N/A
N/A
-40 to 45
85
85
100
115
N/A
N/A
-40 to 50
85
85
100
104
N/A
N/A
-40 to 55
85
84
94
94
N/A
N/A
-40 to 60
84
76
84
84
N/A
N/A
-40 to +65
76
69
76
76
N/A
N/A
-40 to +70 *
69
N/A
69
69
N/A
N/A
-40 to 40
85
85
100
135
200
N/A
-40 to 45
85
85
100
135
194
N/A
-40 to 50
85
85
100
135
167
N/A
-40 to 55
85
85
100
135
138
N/A
-40 to 60
85
85
100
110
110
N/A
-40 to +65
85
69
86
86
86
N/A
-40 to +70 *
69
N/A
69
69
69
N/A
-40 to 40
85
85
100
135
200
267
-40 to 45
85
85
100
135
200
221
-40 to 50
85
85
100
135
182
182
-40 to 55
85
85
100
135
149
149
-40 to 60
85
85
100
119
119
119
-40 to +65
85
69
91
91
91
91
-40 to +70 *
69
N/A
69
69
69
69
NOTE
Intrinsic
Safety
/
Non
Ͳ
Sparkin
g
/
Enclosure
dust
cULus
Stainless
Steel
Stainless
Steel High
Temp
Aluminum
* Maximum Ambient Temperature for Inductive alarm = +66 °C
Maximum Process Temperature (°C)
Meter Option
Without Digital Display
With or without Digital Display
Temperature Class