46
Brocade FastIron X Series Chassis Hardware Installation Guide
53-1001723-02
Installation precautions
2
Ground lug, use UL listed Panduit crimp connector, P/N LCD6-10A, and two 10-32, PPH, screws
to secure crimp connector to chassis. The grounding position is located on the side of the chassis
adjacent to the ground symbol.
CAUTION
For the DC input circuit to the system, make sure there is a Listed 30 amp circuit breaker,
minimum -48Vdc, double pole, on the input to the terminal block. The input wiring for connection
to the product should be Listed copper wire, 8 AWG, marked VW-1, and rated minimum 90
degrees celcius.
CAUTION
Use a separate branch circuit for each AC power cord, which provides redundancy in case one of
the circuits fails.
CAUTION
The POE power supply is designed exclusively for use with the
FastIron X Series
POE devices. The
power supply produces extensive power to support 802.3af applications. Installing the power
supply in a device other than the
FastIron X Series
POE will cause extensive damage to your
equipment. Use a separate branch circuit for each AC power cord, which provides redundancy in
case one of the circuits fails.
CAUTION
Ensure that the device does not overload the power circuits, wiring, and over-current protection.
To determine the possibility of overloading the supply circuits, add the ampere (amp) ratings of all
devices installed on the same circuit as the device. Compare this total with the rating limit for the
circuit. The maximum ampere ratings are usually printed on the devices near the input power
connectors.
CAUTION
Make sure the power supply is properly inserted in the slot. Never insert the power supply upside
down.
CAUTION
Do not attempt to install the power supply without first opening the latch on the front of the power
supply. Attempting to install the power supply with a closed latch will result in mechanical
damage to the power supply and power supply slot.