WVRC-8 Installation and Operation Manual
PROGRAMMING
Example:
To enter low and high alarm set points of 30F and 95F, enter 0030/0095.
To enter low and high alarm set points of 10C and 40C enter 1010/1040.
Do not enter
the “/”, it will be entered automatically.
When “6” is selected from the PGM menu, the Status inputs are set up for either
Normally Open or Normally Closed and the required
DEB
ounce time needed before
generating an alarm.
When 1 is selected from the menu: Make changes or press
ESC
ape to accept current
values. If changes are made, all eight values must be entered in sequence.
When 2 is selected from the menu, the following is displayed:
Make changes or press
ESC
to accept current values. If changes are made, all eight
values must be entered must be entered in sequence. Valid settings are 0 through 9. A
“0” will turn off the status input so that it will not generate an alarm. Entering any
number from 1–> 9 will set the “DEBounce” period from 10 to 90 seconds, requiring
the input to be in an alarm state for that amount of time before an alarm is generated.
Any interruption will cause the timer to reset.