Service & Troubleshooting Guide - Home Generator System - Models 040213 and 040234 (15kW)
Section 2 - Troubleshooting Information
Page 30
2
:
Fig. 17 - (FC_3) Low Output Voltage Troubleshooting Flowchart
(FC_3)
Test 1
Measure circuit
breaker load-side
voltage.
240VAC?
No
Yes
Test 2
Measure voltage
at E1 & E2 at CMA
240VAC?
Repair/replace
open wires E1 & E2
between CB output
and CMA
No
Yes
Replace CMA
Test 3
Measure circuit
breaker line
voltage.
240VAC?
No
Yes
Check
Generator Windings
(Page 48)
Cycle CB
Measure CB
Input
Output
OK?
Yes
END
No
Replace
Circuit Breaker
Output
OK?
Yes
No
Output
OK?
Yes
No
END
Output
OK?
Yes
No
Low Output Voltage