4 5 Remote Set Point
4 5 Remote Set Point
SPMD selecting PV1 or PV2 will enable the BTC-2500 to accept a remote set
point signal. If PV1 is selected for SPMD, the remote set point signal is sent to
Input 1, and Input 2 is used for process signal input. If PV2 is selected for
SPMD, the remote set point signal is sent to Input 2, and Input 1 is used for
process signal. To achieve this, set the following parameters in the Setup
menu.
SPMD selecting PV1 or PV2 will enable the BTC-2500 to accept a remote set
point signal. If PV1 is selected for SPMD, the remote set point signal is sent to
Input 1, and Input 2 is used for process signal input. If PV2 is selected for
SPMD, the remote set point signal is sent to Input 2, and Input 1 is used for
process signal. To achieve this, set the following parameters in the Setup
menu.
Case 1: Use Input 2 to accept remote set point
Case 1: Use Input 2 to accept remote set point
Case 2: Use Input 1 to accept remote set point
Case 2: Use Input 1 to accept remote set point
FUNC=FULL
IN2, IN2U, DP2, IN2L, IN2H, are set according to remote signal.
PVMD=PV1
IN1, IN1U, DP1, are set according to the process signal
IN1L, IN1H if available, are set according to the process signal
SPMD= PV2
FUNC=FULL
IN2, IN2U, DP2, IN2L, IN2H, are set according to remote signal.
PVMD=PV1
IN1, IN1U, DP1, are set according to the process signal
IN1L, IN1H if available, are set according to the process signal
SPMD= PV2
FUNC=FULL
IN1, IN1U, DP1, IN1L, IN1H, are set according to remote signal.
PVMD=PV2
IN2, IN2U, DP2, are set according to the process signal
IN2L, IN2H if available, are set according to the process signal
SPMD= PV1
FUNC=FULL
IN1, IN1U, DP1, IN1L, IN1H, are set according to remote signal.
PVMD=PV2
IN2, IN2U, DP2, are set according to the process signal
IN2L, IN2H if available, are set according to the process signal
SPMD= PV1
Note: If PV1 are chosen for both SPMD and PVMD, an
Error Code will
appear. If PV2 are chosen for both SPMD and PVMD, an
Error Code
will appear. You should not use these cases, otherwise, the BTC-2500 will not
control properly.
Note: If PV1 are chosen for both SPMD and PVMD, an
Error Code will
appear. If PV2 are chosen for both SPMD and PVMD, an
Error Code
will appear. You should not use these cases, otherwise, the BTC-2500 will not
control properly.
Setup
FUNC=FULL
SPMD=PV2, PVMD=PV1
or SPMD=PV1, PVMD=PV2
FUNC=FULL
SPMD=PV2, PVMD=PV1
or SPMD=PV1, PVMD=PV2
Error Message
Error Message