3 3 Rearrange User Menu
3 3 Rearrange User Menu
3 4 Display SV Instead of PV
3 4 Display SV Instead of PV
The conventional controllers are designed with a fixed parameters' scrolling. If
you need a more friendly operation to suit your application, the manufacturer
will say " sorry " to you. The BTC-2500 has the flexibility for you to select those
parameters which are most significant to you and put these parameters in the
front of display sequence.
The conventional controllers are designed with a fixed parameters' scrolling. If
you need a more friendly operation to suit your application, the manufacturer
will say " sorry " to you. The BTC-2500 has the flexibility for you to select those
parameters which are most significant to you and put these parameters in the
front of display sequence.
SEL1 : Selects the most significant parameter for view and change.
SEL2 : Selects the 2'nd significant parameter for view and change.
SEL3 : Selects the 3'rd significant parameter for view and change.
SEL4 : Selects the 4'th significant parameter for view and change.
SEL5 : Selects the 5'th significant parameter for view and change.
Range : NONE, TIME, A1.SP, A1.DV, A2.SP, A2.DV, RAMP, OFST,
REFC, SHIF, PB1, TI1, TD1, C.PB, DB, SP2, PB2, TI2, TD2
When using the up-down key to select the parameters, you may not obtain
all of the above parameters. The number of visible parameters is dependent
on the setup condition. The hidden parameters for the specific application are
also deleted from the SEL selection.
SEL1 : Selects the most significant parameter for view and change.
SEL2 : Selects the 2'nd significant parameter for view and change.
SEL3 : Selects the 3'rd significant parameter for view and change.
SEL4 : Selects the 4'th significant parameter for view and change.
SEL5 : Selects the 5'th significant parameter for view and change.
Range : NONE, TIME, A1.SP, A1.DV, A2.SP, A2.DV, RAMP, OFST,
REFC, SHIF, PB1, TI1, TD1, C.PB, DB, SP2, PB2, TI2, TD2
When using the up-down key to select the parameters, you may not obtain
all of the above parameters. The number of visible parameters is dependent
on the setup condition. The hidden parameters for the specific application are
also deleted from the SEL selection.
SEL1
SEL2
SEL3
SEL4
SEL5
Example :
Example :
A1FN selects TIMR
A2FN selects DE.HI
PB1 = 10
TI1 = 0
SEL1 selects TIME
SEL2 selects A2.DV
SEL3 selects OFST
SEL4 selects PB1
SEL5 selects NONE
Now, the upper display scrolling becomes :
A1FN selects TIMR
A2FN selects DE.HI
PB1 = 10
TI1 = 0
SEL1 selects TIME
SEL2 selects A2.DV
SEL3 selects OFST
SEL4 selects PB1
SEL5 selects NONE
Now, the upper display scrolling becomes :
PV
42
UM25001D
In certain applications where set point value (SV) is more important than
process value (PV) for the user, the parameter
( display format ) then can
be used to achieve this purpose.
Press
keys to enter setup menu
, then press
several times
until
appears on the display. If you need the process value to be
displayed, then select
by using
or
key for DISF, If you need set
point value instead of process value to be displayed, then select
for
DISF. Also refer to the flow chart in
to see the location of DISF.
DISF
Section 1-5
In certain applications where set point value (SV) is more important than
process value (PV) for the user, the parameter
( display format ) then can
be used to achieve this purpose.
Press
keys to enter setup menu
, then press
several times
until
appears on the display. If you need the process value to be
displayed, then select
by using
or
key for DISF, If you need set
point value instead of process value to be displayed, then select
for
DISF. Also refer to the flow chart in
to see the location of DISF.
DISF
Section 1-5
DISF
has two values:
Display process
value
Display set point
value