11 - PROGRAMMING THE FROST PRO-
TECTION TEMPERATURE
-
Open the cover.
-
Press the
button and verify that the
same symbol appears on the display (fig. 33).
The display shows the default frost protection
temperature (3°C) which will remain displayed
for 5 seconds (fig. 33).
-
Press the or button to select any
temperature between 3°C and 16°C (fig. 34).
-
Press the
button to exit and save the
new temperature to memory.
-
Close the cover.
12 - TEMPERATURE MEASUREMENT
CALIBRATION
-
Make sure that the unit is in OFF mode.
-
Press button
P
(fig. 35).
The word
will appear on the display.
-
Press the buttons (forward) o (back-
wards) (fig. 36) until the desired value of
correction is arrived at.
Pressing either of the arrows will cause the
word
to disappear to be replaced by the
correction value to be applied.
10 seconds after the last action the unit exits
the procedure and accepts as valid the data
inserted up to that moment.