Solution 64 | Installer Guide | Programming Overview
4-4
Bosch Security Systems | 11/05 | BLCC110I
Zone Array
The feature allows you to view the condition of all zones on
the panel in banks of 16 zones at a time. From the installer
programing mode press MENU 3-0-1 to access the zone array.
Use the up and down arrow keys to scroll up and down the
zone banks and Press [OK] or [MENU] when finished.
The following information can be displayed depending on the
current zone status.
N
= NORMAL
S
= SHORTED
A
= ALARM
T
= TAMPER
-
= DISABLED
0000000001111111
1234567890123456
NSA-ANAT--------
PRESS
, OK or MENU
In the above example screen,
N
= Zone 01 and 06 are Normal (Sealed)
S
= Zone 02 is Shorted
A
= Zone 03,05,07 are in Alarm (Unsealed)
T
= Zone 08 is in Tamper Alarm (Unsealed)
-
= Zone 04, 09-16 are Disabled (Unused)
Testing the System
You will need to be in programming mode before accessing
the test functions listed below.
Walk Test
Use the walk test command MENU 3-9-0 to test and verify that
all zones work correctly.
External Audible Test
Use MENU 4-9-0 to test and verify that all horn speakers
operate. This test will sound the horn speaker for two seconds.
Internal Audible Test
Use MENU 4-9-1 to test and verify that all 12 VDC sirens
operate. This test will sound the siren for two seconds.
Strobe Test
Use MENU 4-9-2 To test and verify that the strobe operates.
This test will turn on the strobe until you manually stop the
test.
Battery Test
Use MENU 7-9-1 to test the back-up battery that is connected
to the control panel.
Communication Test
Use MENU 5-9-0 to test the telephone reporting capability of
the control panel. You can also activate a communication test
by holding down the Test / Mail key on the keypad.
Basic Reporting Reference
The following table is a shortform point ID listing.
For a complete listing of all the CID and SIA event reporting
information that will be sent by the Solution Control panel
contact your distributor or visit www.Bosch.com.au.
Point ID Table
Module Description
Ur999
Installer
Ur001 - 256
Users
Ur000
Quick Arm
Zn999
Keyfob Low Battery
Zn998
Keyfob Panic Alarm
Zn891-898
Panels 1-8
Zn881-888
Keypads 1-8
Zn871-878
Ethernet 1-8
Zn861-868
GSM 1-8
Zn851-858
Output Expander 1-8
Zn841-848
Serial Expander 1-8
Zn831-838
Lan P/Supply 1-8
Zn821-828
RF Reciever 1-8
Zn811-818
Access 1-8
Zn801-808
X10 1-8
Zn791-798
Lift 1-8
Zn001-128
Zones
Table 13: Shortform Point ID Listing