REFUspeed RS51
Operator control and visualization
6-3
DOK-RD500*-RS51*******-IB02-EN-P
Parameterization using the operator panel
The basic parameterization is described in more detail in Section 7.
Key
Menu level
Parameterizing level
Esc
Return jump to the previous
menu item
The modified value is rejected
Mon
Changes into the monitor
Prog
Changes into parameteriza-
tion
The value is initially accepted. All of
the values are only accepted after
the “Enter” key has been pressed.
Enter
Accepts the selected
menu item
Accepts the modified value
To the previous menu item
Increases the value
To the next menu item
Decreases the value
Jump to the end of the list
Cursor position to the right
Jump to the beginning of
the list
Cursor position to the left
Fig. 6-4: Key functions of the operator panel when parameterizing
Fast parameterizing using key combinations
Key
Response
The first selection parameter is directly selected for text parameters.
+
When these keys are simultaneously pressed:
– the complete parameter number is set to zero
(numerical list).
– the complete parameter value is set to zero (for numerical
parameters).
– the text selection is scrolled in steps of ten (this is practical,
e.g. parameter P0875 with almost 100 selection texts).
The last selected text is selected for text parameters.
+
When these keys are simultaneously pressed, the active value is set to the factory setting.
Mon
+
Prog
If these keys are simultaneously pressed, the system changes from the Mon or Prog area into
a temporary actual value display.
When the ESC key is pressed again, the display switches-back to the selected menu. In or-
der that the operator can differentiate between the normal operating display and the tempo-
rary actual value display, the temporary actual value display has a flashing frame.
Fig. 6-5: Key combinations
Error messages when parameterizing
Error message
Cause
Solution
Parameter is not
accessible in the
basic parameterization.
Parameter numbers which are not
accessible have been entered into the
numerical list.
Only pre-defined parameters are available in the
basic parameterization. Only parameter numbers
from the Tables in Section 5 can be entered.
Please
select
basic parameterization
The selected parameter is a macro
parameter and is not accessible in the
free parameterization.
Change into the basic parameterization.
Caution! Data could be lost
.
Parameter inhibited
Drive is operational.
Inhibit the inverter and then change the parameter.
Data conflict
(general)
Some parameter settings are dependent on others. If a parameter is changed and is ac-
knowledged with
Enter
, then data conflicts can occur.