REFUspeed RS51
Start-up
8-1
DOK-RD500*-RS51*******-IB02-EN-P
8
Start-up
8.1
Steps to prepare for commissioning
The power terminals should be connected-up as specified in Section 5.4,
Power terminals RS51, Sizes J-M and the control terminals as specified in
Section 5.6, Control terminals.
Check whether the star / delta jumpers have been correctly connected at
the motor terminal board.
Observe the “Hazardous voltage warning information” in Section Fehler!
Verweisquelle konnte nicht gefunden werden.!
It should also be ensured that signal, line supply and motor feeder cables
have been separately routed with a minimum clearance between them!
The setpoint cables must be shielded. Please refer to Section Fehler!
Verweisquelle konnte nicht gefunden werden., Fehler! Verweisquelle
konnte nicht gefunden werden..
Before commissioning the electrical system for the first time, a qualified
electrician or engineer should first check that the equipment corresponds,
both electrically and mechanically, to the safety requirements (5 Para-
graph 1 No. 1 VBG 4), specified by
•
the accident prevention regulations,
•
and the general electrical regulations.
Check whether a rotating motor could cause human injury or material
damage!
The power and control voltages can be switched-in after all of the control,
setpoint and power supply cables have been connected. The operator
panel displays the “Switch-on enable” message after approx. 10 seconds.
8.2
Procedure when first commissioning the drive system
The factory setting is always assumed regarding the parameterization in
the “Commissioning” section.
The following diagram guides you through the simplest start-up using the
Quick-Setup and starting the drive with the factory settings.
The second route represents, as an example, several settings per
“Prompted parameterization”. Please refer to Section 7 in these Operating
Instructions for all other possibilities of parameterizing the drive.
The factory settings of the parameterization are also provided in Section 7
in the tables.