4-2
Mounting
REFUspeed RS51
DOK-RD500*-RS51*******-IB02-EN-P
4.2
Mounting, drives sizes J to M
•
The REFUdrive 500 drives, sizes J to M are module and are designed
for installation in cabinets.
•
The drive units have mechanical grid dimensions of 22.5 mm. Several
drive units can be mounted next to one another without any intermedi-
ate space when using mounting rails with threaded holes with the di-
mension grid (also refer to the mounting example).
•
The drives must be mounted vertically onto a flat surface.
•
A minimum clearance of 100 mm above and below the drives must be
maintained to ensure an unrestricted cooling airflow.
•
When mounted in cabinets, the cooling airflow requirement of the in-
stalled drives must be calculated and the cabinet ventilation appropri-
ately dimensioned.
•
The mounting bolts are specified in the drilling templates of the dimen-
sion drawings.
Minimum clearance
Cooling air
Hot discharged air
100 mm
Minimum clearance
for cooling
100 mm
Minimum clearance
for cooling
Fig. 4-2: Minimum clearance for cooling