REFUspeed RS51
Electrical installation
5-5
DOK-RD500*-RS51*******-IB02-EN-P
Power supply connection
Motor connection
Drive unit
output
Recommended
minimum cross-
section
Cable cross-
section which can be
connected 1)
Maximum
fusing, type
Typ gL
Recom-
mended
minimum
cross-section
Cable cross-
section which
can be con-
nected 1)
[kVA]
[mm
2
]
[mm
2
]
[A]
[mm
2
]
[mm
2
]
3
1.5
0.2 - 4
5
1.5
0.5 - 10
6
2.5
0.2 - 4
10
2.5
0.5 - 10
14
4
0.2 - 4
20
4
0.5 - 10
24
10
6 - 25
35
10
10 - 25
31
16
6 - 25
50
16
10 - 25
50
35
25 - 50
80
35
16 - 50
1):
As a result of the terminal size
Fig. 5-1: Cable cross-sections for line supply, DC link and motor feeder cables
5.4
Power terminals RS51, Sizes J-M
Terminal layout diagram, sizes J - M
Note:
The supplementary function P24V, electronics standby supply
(terminal X83) is only mounted if it was actually ordered. It can
only be retrofitted by extremely well-trained personnel.