6-4
Operator control and visualization
REFUspeed RS51
DOK-RD500*-RS51*******-IB02-EN-P
Error message
Cause
Solution
Data conflict
e.g. P0182 with P0183
The V/Hz characteristics are not cor-
rect. The frequencies must have a
minimum
1 Hz clearance between them.
Initially accept the value of the first parameter
change with
Prog
after the second parameter
change acknowledge with
Enter
to save.
Data conflict
e.g. P0870
steady-state<==>dynam
Changing the “steady-state” into the
“dynamic On/Off command” or vice
versa. Steady-state / dynamic On/Off
operation for the test / normal operat-
ing modes cannot be selected, mixed.
Initially accept the value of the first parameter
change with
Prog
, after the second parameter
change acknowledge with
Enter
to save.
Fig. 6-6: Error messages when parameterizing
Load Standard Values
When the drive converter or inverter is supplied, the parameters are set to
standard values. The “Load factory setting” function can also be activated
by parameter P0071.
SET PARAMETERS
Prompted parameterization
Unit setting
P0071 Load factorySetting
No action
Basic parametrizat.
Free parametrizat.
NAMUR applic. basic
Sercos applic. free
Note:
All of the parameters of the selected password level are reset
using the “Load factory setting” function.
Copy Function
A copy function is integrated in the user panel. This allows a parameter
set to be saved in the user panel (P0733) and then transferred quickly into
another unit (P0732). In this case, only those parameters which are ac-
cessible with the selected password level are transferred to the unit.
Note:
The parameter set can be saved in the operator panel after
start-up and after the drive has been optimized. This means
that when the AC drive converter is replaced, it can be quickly
recommissioned.
Password level 3 must be used to transfer (download) data
into the drive.