IPC 40.2
Software
9-5
DOK-SUPPL*-IPC*40.2***-PR02-EN-P
After calling up
UPS Properties and Maintenance
, first, the
UPS
General
tab is active, with which the basic settings of the starting and run
time behavior of the UPS are specified.
upsc5-general.BMP
Fig. 9-5:
"UPS General" tab
Note:
To activate parameter modifications the UPS program is
automatically stopped and re-started During this time
(5...10 sec) no monitoring takes place.
COM Port:
At this place, the serial communication interface is selected,
to which the UPS is connected. If in BIOS one or more serial interfaces
are deactivated, the remaining interfaces of Windows NT are re-
numbered. Therefore, a new interface must be selected in the
configuration dialog under COM port. If no interface is found during the
starting process of the service, a corresponding dialog is opened and the
service is terminated.
In the range
Advanced Controls
the following settings are possible:
Shutdown Delay Time:
Here, a delay time for the shutdown from 0...45 s
is determined. This is the time the user has to back up his data. After the
expiration of the delay time all application programs are terminated
without safety prompt.
When you determine the
Shutdown Delay Time,
observe that between
the end of the
Shutdown Delay Time
and the expiration of the 60
seconds after the power down signal remains enough time to shut down
the operating system (for closing the Windows system files and
generating backups). If the time is too short, the shutdown process is
interrupted, because the UPS interrupts the voltage of the power supply
unit. This can cause a loss of data.
UPS General
Summary of Contents for Rexroth IPC 40.2
Page 6: ...IV Contents IPC 40 2 DOK SUPPL IPC 40 2 PR02 EN P ...
Page 26: ...4 6 Technical Data IPC 40 2 DOK SUPPL IPC 40 2 PR02 EN P ...
Page 54: ...8 10 Maintenance and Installation IPC 40 2 DOK SUPPL IPC 40 2 PR02 EN P ...
Page 74: ...12 4 Index IPC 40 2 DOK SUPPL IPC 40 2 PR02 EN P ...
Page 81: ......