6-2
Display and Operating Components
IPC 40.2
DOK-SUPPL*-IPC*40.2***-PR02-EN-P
6.2
Operating and Error Indication
In the upper right part of the connector panel there are five LEDs to
indicate the device states and errors. Start the measure specified in the
following table, if one of the succeeding LEDs indicates an error or a note.
LED
Indicator
Meaning
Measure
LED
green
Normal mode
-
Vi
LED OFF
No supply voltage
230/115 VAC or 24 VDC
Check supply voltage at
the power supply unit!
LED
green
Normal mode
-
Vo
LED OFF
Internal 5 V supply faulty!
-
LED OFF
Normal mode
T
LED
yellow
flashing
Over-temperature
Reduce ambient
temperature
(surrounding air
temperature)!
Check fan at the PC!
LED OFF
Normal mode
-
LED red
Industrial PC is currently
operating in battery mode,
i. e. no power supply
available!
Restore power supply
and initiate controlled
BTV restart!
UPS
LED red
flashing
Battery pack discharged,
defective or not connected
Check battery pack!
Maintain the charging
time of 5 hours!
HDD
LED
yellow
Hard disk access
-
Fig. 6-1:
LEDs to indicate operations and errors on the connector panel