IPC 40.2
Technical Data
4-3
DOK-SUPPL*-IPC*40.2***-PR02-EN-P
4.4 Ambient
Conditions
Operation
Storage/transport
Max. ambient temperature
(surrounding air temperature)
+5 °C... +45 °C
-20 °C to +60 °C
Max. temperature gradient
Temporal temperature changes up to 3 °C
per minute
Not defined
Relative humidity
Climatic class 3K3 according to
EN 60721, condensation not permissible.
Climatic class 3K3 according to
EN 60721, condensation not permissible.
Air pressure
Up to 2000 m above sea level according
to DIN 60204
Mechanical strength
Max. vibration:
Frequency range: 10 ... 150 Hz
Excursion:
0.075 mm
for 10 ... 57 Hz
Acceleration:
1 g
for 57 ... 150 Hz
According to EN 60068-2-6
Max. shock:
15 g according to
DIN IEC 68-2-27,
no disturbance of the function
Fig. 4-4:
Ambient conditions
4.5 Used
Standards
The system components of the IPC 40.2 correspond to the following
standards:
Standard
Meaning
EN 60,204-1
Electrical equipment of machines
EN 50,081-2
Basic technical standard, emitted interference
(industrial environment)
EN 50,082-2
Basic technical standard, noise immunity (industrial
environment)
EN 60,742
Transformer for 24 V power supply unit, protective
separation
EN 60,950
Overvoltage category II
EN 61,131
Requirements concerning the 24 V outputs
EN 61 131-2
Requirements concerning the 24 power supply
EN 418
Machine safety, EMERGENCY STOP devices
EN 60 529
Degrees of protection (incl. housings and installation
compartments)
EN 60 068-2-6
Vibration test
EN 60 068-2-27
Shock test
Fig. 4-5:
Used standards
Note:
Concerning delivered IPC
40.2 all CE requirements are
fulfilled. After plugging-in extension cards, however, a new CE
test has to be executed.
Summary of Contents for Rexroth IPC 40.2
Page 6: ...IV Contents IPC 40 2 DOK SUPPL IPC 40 2 PR02 EN P ...
Page 26: ...4 6 Technical Data IPC 40 2 DOK SUPPL IPC 40 2 PR02 EN P ...
Page 54: ...8 10 Maintenance and Installation IPC 40 2 DOK SUPPL IPC 40 2 PR02 EN P ...
Page 74: ...12 4 Index IPC 40 2 DOK SUPPL IPC 40 2 PR02 EN P ...
Page 81: ......