Error code Error argu‐
ment
Cause
Troubleshooting
10
Error in parameter database
of the field bus coupler
Restart by disconnecting the
power supply and then re‐
connecting it. Contact
Bosch Rexroth Service if the
problem persists
11
Version of parameter
database is not supported
12
Number of I/O modules
does not match number en‐
tered into the parameter da‐
tabase (I/O module re‐
moved or deleted)
13
Error in parameter database
of the field bus coupler
14
Internal error
Restart by disconnecting the
power supply and then re‐
connecting it. Contact
Bosch Rexroth Service if the
problem persists
15
16
20
Ordering numbers of I/O
modules differ from the
numbers saved in the pa‐
rameter database (e.g. S67-
AI4-U/I-M12 instead of S67-
AI4-RTD-M12)
Replace the I/O module with
the one with the correct or‐
dering number
23
Internal error
Restart by disconnecting the
power supply and then re‐
connecting it. Contact
Bosch Rexroth Service if the
problem persists
24
25
The saved parameters can‐
not be applied to the I/O
module, as
- there is an incompatible
firmware release (after cre‐
ating the parameter data‐
base, one or more modules
were replaced from an
IndraControl S67 node.
These modules have an in‐
compatible firmware release
compared to the original
ones)
or
- a communication error oc‐
curred
Restart by disconnecting the
power supply and then re‐
connecting it
30
Error in parameter database
of the field bus coupler
Restart by disconnecting the
power supply and then re‐
connecting it. Contact
Bosch Rexroth Service if the
problem persists
DOK-CONTRL-S67S3BKDI8*-AP03-EN-P
Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs (M8)
Bosch Rexroth AG
115/139
Diagnostics