S67-DIO8-M8/S67-DIO8-M12x8 (8 DIO + X Counter)
IndraControl S67 I/O-Modul (IOM)
S-0-1502.x.0 „Digital Output“
S-0-1503.x.0 „Digital Input“
IDN/S-0-1503.x.1 „Name of IO_FG“
IDN/S-0-1503.x.2 „Configuration of IO_FG“
IDN/S-0-1503.x.7 „Channel quantity PDIN“
IDN/S-0-1503.x.8 „Channel width PDIN“
IDN/S-0-1503.x.9 „PDIN“
IDN/S-0-15XX.SI.SE „Optional Parameter“
IDN/S-0-15XX.SI.SE „Standard Parameter“
IDN/S-0-1502.x.1 „Name of IO_FG“
IDN/S-0-1502.x.2 „Configuration of IO_FG“
IDN/S-0-1502.x.11 „Channel quantity DIAGOUT“
IDN/S-0-1502.x.12 „Channel width DIAGOUT“
IDN/S-0-1502.x.13 „DIAGOUT“
IDN/S-0-1502.x.15 „Channel quantity DIAGIN“
IDN/S-0-1502.x.16 „Channel width DIAGIN“
IDN/S-0-1502.x.17 „DIAGIN“
IDN/S-0-1502.x.3 „Channel quantity PDOUT“
IDN/S-0-1502.x.4 „Channel width PDOUT“
IDN/S-0-1502.x.5 „PDOUT“
S-0-1506.x.0 „Counter“
IDN/S-0-1506.x.1 „Name of IO_FG“
IDN/S-0-1506.x.2 „Configuration of IO_FG“
IDN/S-0-1506.x.7 „Channel quantity PDIN“
IDN/S-0-1506.x.8 „Channel width PDIN“
IDN/S-0-1506.x.9 „PDIN“
IDN/S-0-1506.x.3 „Channel quantity PDOUT“
IDN/S-0-1506.x.4 „Channel width PDOUT“
IDN/S-0-1506.x.5 „PDOUT“
IDN/S-0-1501.x.20 „Parameter Channel Transmit“
IDN/S-0-1501.x.19 „Parameter Channel Receive“
Fig. 9-3:
Representation of the IndraControl S67 I/O module S67-DIO8-M8/
S67-DIO8-M12x8 in the FSP_IO
The 8 digital input and output channels are displayed here by the function
groups S-0-1502 "digital output" and S-0-1503 "digital input" of the same
name and the counter data is displayed by the additional function group
S-0-1506 "counter".
The optional diagnostic parameters IDN/IO_FG.x.13 "DIAGOUT" and IDN/
IO_FG.x.17 "DIAGIN" are always assigned to the function group with the
smallest number, in this example S-0-1502 "digital output".
9.2
Addressing (Sercos Address)
The Sercos address is automatically assigned by the Sercos master in CP2
or set manually on the IndraControl S67 field bus coupler by the address se‐
lector switch on the top of the housing (under the transparent protective dust
cover). In its delivery status, the address selector switch is deactivated and
the Sercos address has the value 1. More information on the address switch
is located in
chapter 4.5 "Address and Operation Mode Switch (DIP Switch)"
.
Automatic address assignment
To use the automatic assignment function for the Sercos address, the ad‐
dress selector switch is to be deactivated (switch 10 in position ON). The
Sercos address is automatically assigned by the write access to parameter
IDN/S-0-1040 "Sercos address". The written address is immediately activated
and permanently saved in the coupler. This address is automatically reactiva‐
ted after another power-on-reset.
Manual address assignment
To use the manual assignment function for the Sercos address, the address
selector switch is to be activated (switch 10 in position OFF). Using switches
1 … 9, the desired Sercos address can now be configured in BCD coding.
Bosch Rexroth AG
DOK-CONTRL-S67S3BKDI8*-AP03-EN-P
Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs (M8)
90/139
Sercos