Bosch Flue and Ventilation Quick Reference Guide 2022
Whilst it is always our intention to fully assist, it is essential to recognise that all information given by the company in response to an enquiry of any nature is provided in good faith and based
upon the information provided with the enquiry. We recommend that advice should always be checked with your installer or contract partner. Consequently, the company cannot be held
responsible for any liability relating to the use or repetition of such information or part thereof. In addition, whilst making every reasonable effort to monitor the performance and quality of
our supply, installation and service network, we do not accept responsibility for the workmanship or operation of any third party company that the company may have promoted either in
conversation, e-mail, or other communication. Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole.
You can find this, and all issued technical bulletins on the Worcester website at:
1
Worcester, Bosch Group, Cotswold Way, Warndon, Worcester WR4 9SW Technical Services: 0330 123 3366 | [email protected]
Air supply and ventilation quick referencing guide for the Worcester Bosch GC 7000
WP – covering
BS5440-2:2009
,
BS6644:2011
and
IGEM-UP-10 (Edition 4)
.
Ventilation
Air supply and ventilation within a
domestic installation
– quick referencing guide to meet
BS5440-2:2009
(supply only to single boilers).
With reference to any boiler below 70 kW Input (GC 7000 WP 50 kW & 65 kW condensing boilers only).
Please note:
Groups of boilers exceeding 70 kW net are covered by IGEM-UP-10 (Edition 4) and BS6644:2011.
Total rated net input must not exceed 70 kW
Natural ventilation for open flued appliances installed within a room.
BOILER TYPE
NET HEAT INPUT
VENTILATION ROUTE
ROOM 1
ROOM 2
ROOM 3
GC 7000 WP 50 kW
47.5 kW
Ventilation for room containing
appliance
203 cm²
N/A
N/A
Ventilation through 1 additional
room
304 cm²
203 cm²
N/A
Ventilation through 2 additional
rooms
304 cm²
304 cm²
203 cm²
GC 7000 WP 65 kW
64.3 kW
Ventilation for room containing
appliance
287 cm²
N/A
N/A
Ventilation through 1 additional
room
430 cm²
287 cm²
N/A
Ventilation through 2 additional
rooms
430 cm²
430 cm²
287 cm²
Natural ventilation for open flued appliances installed within an enclosure.
VENTILATION ROUTE / GRILLE LOCATION
VENTILATION TO A ROOM OR INTERNAL SPACE
(THE ROOM OR INTERNAL SPACE VENTILATION MUST BE
VENTILATED AS DETAILED ABOVE TO THE OUTSIDE AIR)
VENTILATION DIRECT TO OUTSIDE AIR
High level (free area cm² per kW net heat input)
cm²
10
5
Low level (free area cm² per kW net heat input)
cm²
20
10
Natural ventilation for room sealed appliances installed within an enclosure.
VENTILATION ROUTE / GRILLE LOCATION
VENTILATION TO A ROOM OR INTERNAL SPACE
VENTILATION DIRECT TO OUTSIDE AIR
High level (free area cm² per kW net heat input)
cm²
10
5
Low level (free area cm² per kW net heat input)
cm²
10
5
This example shows an installation
where the GC 7000 WP 50 kW boiler
is placed within a room adjacent to
two additional rooms.
The two adjacent rooms will have the
larger ventilation installed.
A) & B) Represents high-level and
low-level vent arrangement for an
open flue within a compartment. See
tables below for vent sizing based on
net heat input.
e.g.,
47.5 kW x 10cm² = 475cm²
High level ventilation to a room or
internal space.