40
en | Alarm
Panel Controller
F.01U.076.969 | 6.0 | 2010.04
Operation guide
Bosch Sicherheitssysteme GmbH
8.3
Day and night mode
Depending on the configuration, an incoming alarm is handled differently in day and night
mode:
Night mode
Night mode has the highest security level. Depending on the configuration, the alarm message
is generally transmitted to the fire department without a delay.
Signaling devices (e.g. sirens) and transmission devices to the fire department or fire
protection systems are activated.
If the transmission device to the fire department is activated, the "Transmission Device
activated" LED display lights up red:
Depending on the configuration, a detector in night mode triggers a pre-alarm if intermediate
alarm storage is used as an alarm delay for this detector.
Day mode
Depending on the configuration, a distinction is made between the following possible alarm
delays in day mode:
–
Alarm verification
–
Pre-alarm
Depending on the configuration, a pre-alarm is displayed for the following alarm delays:
–
Intermediate alarm storage
–
Dual-detector dependency
–
Dual-zone dependency
For a detailed description of the various alarm delays, see
Section 8.2 Entry delays
.
–
Internal alarm
An alarm that is reported to the panel in day mode. No transmission devices to the fire
department are activated.
NOTICE!
Depending on the configuration, the manner in which the difference between day and night
mode is displayed may differ from that on the system.
NOTICE!
Depending on the security level in question, not all detectors can be switched to day mode.