en | Fire alarm
Panel Controller
F.01U.076.969 | 6.0 | 2010.04
Operation guide
Bosch Sicherheitssysteme GmbH
If different elements are offered for resetting:
1.
Select an element. At the menu items Zone and Detector, a list with all the logical zones
and detectors concerned appears.
2.
Select the list field you require. Refer to
Section 5.6.1 Scrolling through lists, page 28
for
information on how to scroll forward and backward through a list.
The list field is marked.
3.
Select
Reset
.
The selected element / element group is reset.
If a list field is marked with an R, the process of resetting is not yet complete for this element.
If an element cannot be reset, it will continue to be displayed in the list.
After the successful resetting of all elements, the standby display is displayed.
9.8
Bypassing detectors
To bypass a detector that has triggered an alarm:
1.
Select the alarm message you require.
2.
Select
Bypass
.
TEXT
R
NOTICE!
The system does not transmit any information as to whether it was possible to bypass the
selected element. To monitor the operation, please check the element.