54
en | Bypass
Panel Controller
F.01U.076.969 | 6.0 | 2010.04
Operation guide
Bosch Sicherheitssysteme GmbH
11
Bypass
This chapter contains information about the following points:
–
Section 11.2 Bypassing and un-bypassing elements, page 54
–
Section 11.3 Displaying and un-bypassing bypassed element groups, page 55
–
Section 11.4 Displaying list of all bypassed elements, page 55
–
Section 11.5 Bypassing/Un-bypassing buzzer, page 56
11.1
Menu overview
11.2
Bypassing and un-bypassing elements
Select the element you require in the submenu.
Example:
To bypass a detector, select the following in the start menu:
1.
Bypass Block
2.
Bypass
3.
Detector
Various sorting criteria are displayed. See also
Section 5.6 Working with lists, page 27
.
4.
Select a selection criterion, e.g.
By description
.
A list of the detectors is displayed. Refer to
Section 5.6.1 Scrolling through lists, page 28
for information on how to scroll forward and backward through the list.
5.
Select the required list fields.
The list fields are marked.
WARNING!
Bypassed detectors: Alarm messages from bypassed detectors are no longer displayed, only
faults.
Isolated detectors: Isolated detectors are not analyzed.
Bypass
Block
->
Bypass
-> Show bypassed devices Select by
number
Bypass buzzer
Printer
Block
Signalling devices
Transmission
device
HVAC
Doorholder
Detector
Logical zone
Extinguishing
system
Annunciator
Bypass group
More...
->
Control element Interface
module
NOTICE!
Partly bypassed elements, such as loops or bypass groups, can be displayed and completely
bypassed; see
Section 11.3 Displaying and un-bypassing bypassed element groups, page 55
.
NOTICE!
The menu structure may be different depending on the configuration in FSP-5000-RPS.