70
en | Maintenance – walktest
Panel Controller
F.01U.076.969 | 6.0 | 2010.04
Operation guide
Bosch Sicherheitssysteme GmbH
Example:
1.
Select
Show / Change
.
To delete one or more element(s) from the selected group:
2.
Select one or more list fields.
The list fields are marked. Refer to
Section 5.6.1 Scrolling through lists, page 28
for
information on how to navigate through a list.
3.
Select
Delete
.
The element is deleted from the selected group. The list field is no longer displayed.
In order to add new elements:
1.
Select
New
.
The display changes. Various element categories containing elements which have not
been assigned to any walktest group yet are displayed.
2.
Select the element category you require.
3.
Select one or more list fields.
The list fields are marked.
4.
Select
Add
The selected element is added to the selected walktest group.
Change name
To change the name of the input or output group:
1.
Overwrite the name; see
Section 5.8 Entering numbers and text, page 31
.
2.
Select
OK
.
The new name is confirmed.
15.2
Starting and ending walktest
15.2.1
Starting the walktest
To select the elements for the walktest and to switch them to walktest:
1.
Select
Maintenance
from the start menu
2.
Walktest
3.
Start / End walktest
Various element categories are displayed.
4.
Select:
–
More...
to display further categories or
–
to select one of the displayed categories or
–
Select by number
and enter the number of the element into the search screen; see
also
Section 5.7 Search Function/Element, page 30
.
NOTICE!
The information about the date and time of every walktest is stored in the history log. You can
print this information on a printer. See
Section 16 Maintenance – history log, page 73
.
NOTICE!
If you select the element category
Loop
,
Logical zone
,
Detector
or
Walktest group
, you will
be asked to select the type of walktest. Select
Sequential walktest
to check each individual
sensor (optical, chemical or thermal) of the detectors you are testing, or select
Simultaneous
walktest
to test combination detectors using a test device with combined trigger substances
for simultaneous testing of multiple sensors.
Summary of Contents for FPA-1200-MPC
Page 1: ...Panel Controller MPC xxxx B FPA 1200 MPC en Operation guide ...
Page 2: ......
Page 93: ......