Analog fire panels
System information | en
19
Bosch Security Systems, Inc.
Installation and Operation Guide
2017.11 | 2.0 | F.01U.173.607
Type Number
Description
FLM-325-I
[CONT-MOD]
Contact Monitors
Designed to use with pull stations, water-flow switches, and other
applications requiring the monitoring of dry-contact alarm-initiating
devices.
Can be programmed in NO EOL, NC EOL, NC no EOL.
Independently from the type, the panel lists only an FLM-325-I.
Two types available for input switches to be connected as Class B:
FLM‑325‑I4 Contact Monitor 4-inch
FLM‑325‑IM Contact Monitor, Mini
Two types available for input switches to be connected as Class A:
FLM‑325‑I4‑AI Contact Monitor 4-inch Class A w/Isolator
FLM‑325‑I4‑A Contact Monitor 4-inch Class A
The types FLM-325-IM, FLM‑325‑I4‑AI, and FLM‑325‑I4‑A can use
addresses 1 to 254.
FLM-325-2I4
[CONT-MOD]
Dual Input Monitor
Provides two independent contact monitoring circuits while utilizing only
one address on the SLC.
Can be programmed to monitor normally open or normally closed contact
fire alarm and supervisory devices (NO EOL, NC EOL, NC no EOL)
Supervises with Style B (Class B), loop powered.
FLM-325-CZM4
[CONVZ-MOD]
Conventional Zone Module
Monitors dry contacts (NO) devices such as two-wire conventional
detectors or pull stations.
Transmits the status of one zone of devices back to the panel
(25 maximum per zone; number depends on type of connected devices).
Class A or Class B wiring is configured with a jumper on the module
Auxiliary (AUX) powered.
For compatible devices, refer to the manual supplied with the product.
The number of Conventional Zone Modules (FLM‑325‑CZM4) for each
SLC module is limited to 32.