44
en | Planning Information
Analog fire panels
2017.11 | 2.0 | F.01U.173.607
Installation and Operation Guide
Bosch Security Systems, Inc.
Program Feature or
Option
Permitted in
UL 864
Possible Settings
Settings Permitted in
UL 864
Primary/Secondary
Account Auto Test
Frequency
Yes
PRIMARY TEST FREQ/
SECOND TEST FREQ
1-Disabled
2-4 HOURS
3-6 HOURS
4-24 HOURS
5-7 DAYS
6-28 DAYS
2-4 HOURS
3-6 HOURS
4-24 HOURS
(depends on version
of standard)
Maximum
Communication Attempts
Yes
MAX ATTEMPTS
3 to 10 attempts (each
line)
5 to 10 attempts total
for both lines
Anti-replay option
No
ANTI-REPLAY
1-ENABLE
2-DISABLE
2-DISABLE
Encryption option for IP
reporting
No
ENCRYPTION ENABLE
1-ENABLE
2-DISABLE
2-DISABLE
Line 1/Line 2 Enable
Yes
1-ENABLED
2-DISABLED
1-ENABLED
Line 1 Ring Count
Yes
0 to 10
0
Tab. 3.27:
Programming requirements according to UL864
Required Accessories
At least one UL Listed smoke detector with a base. At least one horn strobe or bell listed in
the NAC Compatibility List, providing 85 dB for UL864 and NFPA 72 requirements, is required
for this application, and must be installed inside the protected area. Four-wire detectors must
be used with UL Listed power supervision devices. All devices must be used with the End of
Line (EOL) resistor provided.
Configuration Requirements
If alarm verification is enabled, do not mix pull stations and conventional heat detectors on
the same Conventional Zone Module (FLM-325-CZM4).
Notice!
For mixed applications (pull stations and conventional heat detectors connected to the same
FLM‑325‑CZM4 Conventional zone module) use point type “Fire Auto” and “No delay”.
Alarm Verification Requirement
!
Warning!
This unit includes an alarm verification feature that will result in a delay of the system alarm
signal from a smoke detector. The total delay (control unit plus detector) shall not exceed
60 seconds. No other detector type shall be connected to the circuits unless approved by the
Authority Having Jurisdiction.