Analog fire panels
Appendices | en
117
Bosch Security Systems, Inc.
Installation and Operation Guide
2017.11 | 2.0 | F.01U.173.607
Local Panel Settings
AUX power reset
Enabled
External power supply
Disabled
PIN Codes and Authority Levels
Level 1
No PIN (History, Date/time)
Level 2 PIN (maintenance)
2222 (Walk test, Test, Bypass)
Level 3 PIN (programming)
3333
PIN for reset/silence/drill
1111, disabled
Web operator Pin
0000 (user name: “operator”, case sensitive)
Time Schedule
Enable daylight savings
Disabled (Start 1st Sunday in March, End 3rd
Sunday in October)
Detector day sensitivity enabled
Disabled Mo/Tu/We/Th/Fr/Sa/Su
From 7:00 am, To 5:30 pm
Timer Settings
Global delay mode
AV/PAS/Pre-signal
Day mode
No delay
Silence inhibit
0 min
Investigation time
180 s
Alarm verification delay
60 s
Sequential reset delay
5 s
AC failure delay
3 h
Waterflow delay
90 s/ Waterflow silenceable: disabled
Auto silence delay
10 min/ Enable: disabled
Sandwich alarm delay
5 min/ Enable: disabled
Dual zone first alarm reset
60 s/ First alarm latching: enabled
Language, Time Format and Units
Language
English
Timer format
12 h
Units
°F, ft
Function Settings
Silence
Audible only
Supervisory latching
Enabled