84
en | Monitoring, Operating, and Programming
Analog fire panels
2017.11 | 2.0 | F.01U.173.607
Installation and Operation Guide
Bosch Security Systems, Inc.
Piezo Operation
System Status
Silent
The panel is in a normal state (no alarm, supervisory or
trouble condition)
The panel was silenced or acknowledged after an
off‑normal condition
Continuous beep
The panel is in fire alarm condition
Periodic beep (0.5 s on every
2 s)
The panel is in gas alarm condition
Periodic beep (0.5 s on every
4 s)
The panel is in supervisory condition
Periodic beep (0.5 s on every
10 s)
The panel is in trouble condition
Indicates automatic logout within 1 minute if logged in at
Level 1, 2 or 3
Short beep
With every key press
Triple beep
With invalid entries
Tab. 5.42:
Piezo operation
5.4
Keypad Operations
View Status
With no alarms or troubles in the system, the display message is SYSTEM NORMAL along with
the current date and time.
During initialization by start-up or re-configuration, the screen indicates SYSTEM
INITIALYZING.
Upon reset, the panel shows the SYSTEM RESETTING screen until the system returns to the
normal supervising condition.
If PAS or Pre-signal is turned on, the screen indicates SYSTEM NORMAL DAY.
Any off-normal conditions are shown in groups classified as fire alarm, gas alarm, supervisory
and trouble.
Use the arrow keys to view events or conditions in the same group. Up [
∧
] and down [
∨
] keys
move the user to the previous or next event. The left and right keys switch to other groups.
Acknowledge
During an alarm, pressing the Acknowledge [ACK] key turns off the piezo that is sounding on a
keypad or annunciator. All the ongoing events or conditions are marked as Acknowledged. The
24‑hour trouble reminder timer starts. For that, any trouble event not cleared within 24 hours
is sent again and the piezo sounder begins to beep again.
If a fire input point configured as PAS Enabled (with global PAS enabled) is activated, pressing
the Acknowledge [ACK] key within 15 seconds after a PAS activation starts the investigation
timer. This allows the user to investigate the fire alarm or take other appropriate actions until
the timer expires.
An acknowledgement operation can also be initiated by the activation of an input point
configured as an acknowledge type.
To run a lamp test, press and hold the Acknowledge [ACK] key for at least 3 seconds. All LEDs
on the keypad are turned on and the keypad’s LCD display is filled with black boxes. When the
[ACK] key is released, the keypad displays the software revision number, the panel ID, and the
panel’s IP address for 3 seconds. Then the LEDs and display return to normal working mode.