FOCUS
1.3
Display information
Page 10
BOGE FOCUS compressor control for piston compressors
The control system will always save the lowest value. A search for the lowest
value – as a background process – will be restarted once a week. This allows,
after expiry of another week, a higher value compared to the one of the previ-
ous week to be displayed if the measured minimum value has increased dur-
ing that period. Any potential increase of leakages in the compressed air net-
work will therefore also be possible to be determined.
Any power failures during measurement will not be indicated by a sequence of
digits because new values will be calculated every six hours and because any
such power failure during measurement will not prevent the values of the sub-
sequent measurement to be displayed.
If the value next to Lc is blinking and no measurement is intended to be carried
out:
–
Press
INFO key
The value will stop blinking, and the measurement process is not started.
By pressing the
key,
you get to the „Operating times“display.
Info # 1
Pressing the
key
in the operating hours display causes the control display
to show „Info # 1“. This display serves to show information on the compressor
set-up.
Status RS485
1:19200;8N1 The RS485 interface is parameterized as a slave:
address: baud rate, data bits parity stop bits – no com-
munication has taken place as yet.
O.K.
The last communication has taken place less than
1 minute ago.
Time:
This serves to indicate when the last – valid communi-
cation has taken place (up to 7 days).
C2 (C3 C4)
When parameterized as a master and master control
this serves to display which of the compressors are in
communication. Blinking of the combination indicates
defective communication.
On / Off
Local:
via keyboard.
Remote:
via contact and / or Bus.
On:
Compressor is switched on.
Off:
Compressor is switched off.
Output release
Internal:
via internal pressure sensor.
External:
Output release via contact and / or Bus.
Yes:
Output release enabled.
No:
Output lock is active.
Auto-Restart
n / a:
No Auto-Restart after (control) power failure.
Time:
Auto-Restart active, Auto-Restart time.
Note!
Changes to the displayed settings have to be accomplished by means of the
parameter settings, if applicable, (see also chapter „1.4 Settings“, page 13)
or by changing the automatically registered configuration (see also ’Remove
modules and input contacts‘).