BOGE FOCUS compressor control for piston compressors
Page 35
FOCUS
1.10
Parameter overview
P031
After-running time
0 s...600 s
USER
P032
In case of oil lubricated motors:
Monitoring of air temperature = Warning
0 = Fault,
1 = Warning
USER
P042
Suction pressure (booster pressure)
0...174 psi
USER
P044
Message type Oil monitoring
1: Fault, 0: Warning
USER
P050
Modbus address
0 for Master,
2...4 for additional compressors,
1...248 for other applications
USER
P051
Modbus baud rate
1200...115200
USER
P052
Modbus communication parameter
8Even1, 8None1, 8None2, 8Even2, 8Odd1 and
8Odd2
USER
P053
Modbus address (module)
0 for Master,
2...4 for additional compressors,
1...248 for (pure) control applications
USER
P054
Modbus baud rate (module)
1200...115200
USER
P055
Modbus communication parameter (module)
8Even1, 8None1, 8None2, 8Even2, 8Odd1 and
8Odd2
USER
P060
Contact type for compressed air treatment
0: Break contact, 1: Make contact
USER
P061
Message type for compressed air treatment
1: Fault, 0: Warning
USER
P063
External output release
0...2
USER
P064
Monitoring of external output release
0...1
USER
P065
Remote Start-Stop
0...3
USER
P066
Key switch
0...3
USER
P067
Function of input 42
0 = Pressure range, 1 = Monitoring
USER
P070
Number of compressors during base load switching
1...4
USER
P071
Interval time until base load switching
0...250 h
USER
P075
Base load switching: Max. pressure for pressure range 1
0 psi, 58 psi … max. pressure of compressor type
USER
P076
Base load switching: Min. pressure for pressure range 1
44 psi … maximum P075
USER
P077
Base load switching: Max. pressure for pressure range 2
0 psi, 58 psi … max. pressure of compressor type
USER
P078
Base load switching: Min. pressure for pressure range 2
44 psi … maximum P077
USER
No. Meaning
Adjustment
range
Code
level