BOGE FOCUS compressor control for piston compressors
Page 27
FOCUS
1.7
Warning message / Fault message
Example without monitoring and emergency operation function
Four compressors (145 psi), all of which are equipped with a FOCUS control,
are connected by means of RS485 interfaces. The pressure at user's facility
is to be completely released over the weekend and over night and, in addition,
be able to be reduced. Providing sufficient receiver / network volume, the
pressure values can be set according to the following table allowing pressure
reduction by 22 psi which can be actuated by an external contact or by means
of a switch clock – as regards switch clock actuated pressure reduction, also
see Chapter Unplanned compressed air requirement.
1.7 Warning message / Fault message
Warning message /
Fault message
As far as pending messages are concerned there is a difference between
warning and fault messages.
Depending whether an input is defined as fault or warning either only the warn-
ing is displayed ort he compressor is switched off at once via a fault message.
All warning and fault messages are saved by the control in the LogBook to-
gether with operating states and time.
If a message is pending when the control is powered up this is signalled at
once by means of a flashing LED.
In this case the boot display can be left by pressing the
OFF key
,
or you
can get to the main menu by displaying and acknowledging the message.
Even if you leave the boot display via displaying the message, nevertheless
the
OFF key
has to be actuated once
before the control resumes its normal
function.
Warning message
In case of a pending warning or servicing message the compressor remains
in operation and this status is visible by means of a flashing yellow LED.
Press the
INFO button
to display the message type and –number and de-
code the message via the message code list.
The warning can only be acknowledged / pre-acknowledged with the
ENTER
button
in this display. It leads to the main display.
Otherwise, repeated pressing of the
INFO button
leads to displaying of the
compressor state at the time the first unacknowledged (displayed) warning is
triggered. Repeated pressing of the
INFO button
takes you back to the pre-
vious message display – also from other displays (like the main display).
Compressor
Parameter setting in psi
No
P075
P076
P077
P078
P012
P013
P014
P015
P064
1 (Master)
137.8
108.8
116
87
145
129
123
107
0
2
144
128
122
106
0
3
no function
142
126
120
104
0
4
141
125
119
103
0