FOCUS
1.4
Settings
Page 18
BOGE FOCUS compressor control for piston compressors
P061 Message type for compressed air treatment
With this parameter it is determined whether the pending message of the com-
pressed air processing is defined as a warning or as a fault. This setting has
an influence on the performance of the control. Whereas in case of a warning
only a message is released, the compressor is additionally switched off at once
when this parameter is defined as a fault.
In this case setting 1 means fault and setting 0 warning!
P063 External release
The kind of external release is set by this parameter.
If a RS485 module is used and the parameter 53 is parameterized to an ad-
dress higher than 0 – its rotary switch must point to zero in any case – it serves
primarily for external output control prior to the standard Bus.
P064 Monitoring of an external release appliance
The parameter P064 is relevant if the pressure control is effectuated externally
via the digital input and compressed air has to be available continuously – i.e.
no switch-off during the night or on weekends seems to be sensible.
If the parameter P064 is set to the value 0 the monitoring of external output
release is deactivated, if the value 1 is set, the monitoring is active.
In case of activated monitoring the FOCUS automatically switches to internal
pressure control and outputs an appropriate warning message as soon as a
fault of the external control is registered.
P065 Remote Start-Stop
This parameter determines the ON / Off switching function of the control via
TAN, a potential-free contact or the Bus. In case the parameter is selected
unequal 0, a switching On or Off via TAN of the FOCUS is no longer possible.
In case of Remote-On-Off the Auto Restart time (P021) after a power failure is
used for an automatic start delay.
Setting
Meaning
0
Internal release
1
Release via contact
2
Release via contact and an external BUS
Setting
Meaning
0
The On / Off switching is effectuated solely by the control keyboard (local).
1
The On / Off switching is effectuated solely by the input Remote-Start-
Stop-switch (continuous contact).
2
The On / Off switching is effectuated solely by the BUS interface.
3
The On / Off switching is effectuated solely by the continuous contact – re-
lease function – and via the BUS interface, however not via the control
keyboard.