M12 Output Connector 2
PIN
Function
Specifications
Reference
P1
Not Used
P2
Not Used
P3
N.O.
Relay Out, N.O. Contact
6 Amp Max @ 250VAC,
5 Amp MAX @ 30VDC
P4
N.C.
Relay Out, N.C. Contact
6 Amp Max @ 250VAC,
5 Amp MAX @ 30VDC
P5
Ground
Relay Out, COM Contact
M12 Output Connector 3
PIN
Function
Specifications
Reference
P1
Not Used
P2
Not Used
P3
N.O.
Relay Out, N.O. Contact
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P4
N.C.
Relay Out, N.C. Contact
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P5
Ground
Relay Out, COM Contact
Page 17
®
FLEXFLO A4
6.0
Layout
6.5 M12 Connector
M12 Input Connector 1
PIN
Function
Specifications
Reference
P1
Remote Start/Stop
No Voltage
P2
FVS (+)
15 VDC @ 60 mA Supply
Power FVS Sensor
P3
FVS (-)
DC GND (0 VDC)
FVS Ground Input
P4
FVS (Signal)
Input Signal
FVS Input Signal
P5
Ground
DC Ground
0 VDC
P4
P1
P2
P5
M12 Input Connector 2
PIN
Function
Specifications
Reference
P1
Dry Contact
N.O. Dry Contact Closure
Open= Stop Gnd= Run
P2
4-20mA In (+)
120Ω Impedance Loop Ref. to Ground
P3
4-20mA In (-)
DC GND (0 VDC)
P4
Pulse In (+)
0-1000 Hz (AC. Square Wave) Ref. to Ground
FVS Input Signal
P5
Ground
DC GND (0 VDC)
M12 Output Connector 1
PIN
Function
Specifications
Reference
P1
4-20mA Out (+)
250Ohm max load
P2
4-20mA Out (-)
DC GND (0 VDC)
P3
N.O.
Relay Out, N.O. Contact 1 Amp @ 125 VAC
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P4
N.C.
Relay Out, N.C. Contact
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P5
Ground
Relay Out, COM Contact
P1
P4
P5
P3
P2
P3
M12 Input/Output Connector
M12 Profibus Connector
Page 16
®
FLEXFLO A4
6.0
Layout
M12 Output Connector 4
PIN
Function
Specifications
Reference
P1
Pulse Out (+)
0-1000 Hz (AC. Square Wave) Ref. to Ground
P2
Pulse Out (-)
DC GND (0 VDC)
P3
N.O.
Relay Out, N.O. Contact
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P4
N.C.
Relay Out, N.C. Contact
.8 Amp Max @ 30VDC
1 Amp @ 125 VAC
P5
Ground
Relay Out, COM Contact
M12 Profibus Connector
PIN
Function
Specifications
Reference
P1
VP
+5V supply for terminating resisters
P2
RxD/TxD-N
Data line minus (A-line)
P3
DGND
Data ground
P4
RxD/TxD-P
Data line plus (B-line)
P5
Shield
Ground connection
Note:
M12 connectors not included with product.
Input/Output Connectors requires any A-Type M12 connector with 5 position female sockets
Profibus Connectors requires any B-Type M12 connector with 5 position female sockets
If the pump is the last bus device connected to the PROFIBUS cable it must be terminated using terminating resistor
(PROFIBUS standard EN 50170).