The supply voltage should be switched off
at least 10 minutes before accessing
the pump terminal box.
When using an appliance leakage current interrupter (ALCI)
the following should be observed.
– Design according to DIN VDE 0664 (pulse current-sensitive)
– The ALCI must take account of the charging current impulse
when the power is switched on
– The ALCI must be suitable for the leakage current of the pump
(< 3.5 mA)
For momentary voltage surges and uneven phase loads during
the connection process, we recommend a short-delay ALCI.
5.1 Supply terminal
The electronics may be damaged in the event
of incorrect connection or use of the wrong voltage.
When checking the insulation of the installation
The Biral pump must be electrically separated.
The pump may be checked as described
in Chapter 9.
The FI switches have to be marked
with the symbol shown.
5.2 Connecting diagram
AYB
GENIbus interface
(RS485)
T
Twin pump
D
Pressure sensor
and temperature sensor
1-2
External ON/OFF (Start/Stop)
Control contact
for switching pump
on/off externally
3-4
MIN
Min. characteristic curve
5-6
0 –10 V
Analogue input 0 –10 V
5 = +10 V, 6 = 0 V
7-8
Fault message (Alarm)
as NO contact:
closes for fault
Max. load: 250 V AC, 5 A
Mains connection
L
Lead
PE wire,
protective conductor
N
Neutral line
1×230 V +6%/–10%, 50 Hz
1 2 3 4 5 6
+ -
D
T
B
Y
A
N
8
L
7
~1x230V
961341_01
max.250V
5A
➀
For pumps A 802 and A 1002, we recommend
switching via 1/2 (external ON/OFF) contacts.
(Contact closed = pump ON)
➀
Summary of Contents for A 1002
Page 95: ...DIN 4844 W8 DIN 4844 W9 1 1 1 1 2 1 3 1 4 95...
Page 96: ...1 5 1 6 NIN CENELEC 1 7 1 8 1 9 96 2...
Page 99: ...99 961338_00 4 5 961339_00 1 2 1 2...
Page 100: ...100 4 7 75 C 0 6 95 C 1 0 110 C 1 7 500 0 01 100 95 C 0 45 110 C 1 10 961340_00 4 6 7 2...
Page 103: ...103 5 8 6 3 A2 7 2 6 6 1 4 6 2 0 2...
Page 105: ...105 7 1 A1 A1 2 A3 7 5 R100 3 R100 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 7...
Page 107: ...107 t t 7 5 A3 7 6 A 802 A 1002 AD 802 A 802 KW A 1002 KW AD 802 KW 6 6 3 3 24...
Page 108: ...108 8 8 1 R100 7 3 8 2 7 8 c R100...
Page 109: ...109 8 3 0 10 0 10 5 6 2 1 2 3 4 8 4 1 2 3 4 1 3 4 2 3 4 3 4 5 0 10 5 6...
Page 110: ...110 8 5 R100 R100 R100 R100 R100 9...
Page 111: ...111 FI 1 2 1 R100 2 R100 3 3 4 4 R100 4 10 10 7 5...
Page 112: ...112 Biral 7 3 6 2 12 7 3 6 2...
Page 113: ...113 11 11 1 11 2 15 C 110 C B2 DIN 4102 A 802 WD 9 A 1002 WD 10...
Page 115: ......