Set the required address with buttons
.
You can enter address values between 1 and 30.
The set value is automatically adopted after 2 seconds.
6.4.4 Selecting the timer function
The unit provides three different timer functions:
•
Delayed off
(setting “
0
”)
After the defined time has elapsed, the heating is turned off.
•
Temperature-controlled delayed off
(setting “
1
”)
The defined time only begins to run when the current value is by 1 °C below the set point. After the
defined time has expired, the heating is turned off.
•
Delayed on
(setting “
2
”)
After the time set has passed, the heating is turned on and remain in continuous operation.
1.
Press down
button for approx. 5 seconds.
The display alternately shows “unit” and the temperature unit:
2.
Press again button
.
The display alternately shows “rASd” and the set-point gradient:
3.
Press again button
.
The display alternately shows “Adr” and the unit address:
4.
Press again button
The display alternately shows “
tFCt
” and the actual setting of the
timer function
:
5.
Set the desired timer function 0, 1 or 2 with buttons
.
The set value is automatically adopted after 2 seconds.