February 2022
Installation, Operation and Maintenance Manual
VCIOM-15345-EN Rev. 1
56
Customizing Biffi EHO
Section 8: Customizing Biffi EHO
Menu Name
Menu
Key
Configuration/
Calibration Value
Default
Action
FREQUENCY CONFIGURATION
The power supply frequency configuration.
Note: This will be factory set.
Fc
0 = DC
1 = 50 Hz
2 = 60 Hz
3 = Not defined
Feedback Only
PHASE CONFIGURATION
The power supply phase configuration.
Note: This will be factory set.
Pc
0 = Single Phase
1 = Three-Phase
Feedback Only
HYDRAULIC LEAK ALARM DEBOUNCE COUNT
Set the maximum number of Valve Drift
Alarms allowed per hour. If Valve Drift Alarm
Frequency is more than the Hydraulic leak
Alarm Debounce Count, then the Hydraulic
Leak Alarm will be generated. If Valve Drift
Alarm is less than the Hydraulic Leak Alarm
Debounce Count then Hydraulic Leak Alarm
will be automatically cleared.
dC
2 to 10
2
LOW OIL ALARM ENABLE
If oil level sensor is present, then this
parameter can be used to Enable or
Disable the Low Oil Alarm.
LO
0 = Disable
1 = Enable
Feedback Only
DISCRETE INPUT SETUP
Set the discrete input logic.
di
Yes/No
N/A
DISCRETE INPUT 1
Set if Discrete Input for OPEN command
should be Active on Close contact or
Open Contact.
d1
0 = Active on Close contact
1 = Active on Open contact
0 = Active on
Close contact
DISCRETE INPUT 2
Set if Discrete Input for CLOSE command
should be Active on Close contact or
Open Contact
d2
0 = Active on Close contact
1 = Active on Open contact
0 = Active on
Close contact
DISCRETE INPUT 3
Set if Discrete Input for STOP/PST command
should be Active on Close contact or
Open Contact.
d3
0 = Active on Close contact
1 = Active on Open contact
0 = Active on
Close contact
DISCRETE INPUT 4
Set if Discrete Input for OPEN INHIBIT
command or OIL LEVEL SENSOR input should
be Active on Close contact or Open Contact.
d4
0 = Active on Close contact
1 = Active on Open contact
0 = Active on
Close contact
DISCRETE INPUT 5
Set if Discrete Input for CLOSE INHIBIT
command should be Active on Close
contact or Open Contact.
d5
0 = Active on Close contact
1 = Active on Open contact
0 = Active on
Close contact
DISCRETE OUTPUT SETUP
Set the configurable output relays customer can
use to monitor for various parameters. Refer to
wiring diagram for relay terminal connection.
dO
Yes/Nov
N/A