February 2022
Installation, Operation and Maintenance Manual
VCIOM-15345-EN Rev. 1
64
Customizing Biffi EHO
Section 8: Customizing Biffi EHO
Menu Name
Menu
Key
Configuration/
Calibration Value
Default
Action
CALIBRATE LOWER LIMIT OF ANALOG
OUTPUT 2
Calibrate the Analog Output 2 Channel
for 4 mA equivalent value. The channel
output needs to be monitored externally.
oL
Yes/No
N/A
ANALOG OUTPUT 2 CALIBRATION CHOICE
Select if the Analog Output 2 needs to be
increased or decreased.
cC
0 = Increment
1 = Decrement
0 = Increment
CALIBRATING ANALOG OUTPUT 2
The Analog Output can be changed based
on selection at [c][C] menu. 'Yes' option
at this menu means accept the output.
'No' option at this menu will increase or
decrease the output.
c2
Yes/No
N/A
CALIBRATION PASSED FOR LOWER LIMIT
(CALIBRATION STATUS)
The Analog Output 2 channel is calibrated
for the desired output.
cL
N/A
Analog Output 2
Calibration Status. Not
Searchable/Configurable
CALIBRATED FAILED (CALIBRATION STATUS)
Calibration for Analog Output 2 channel has
failed. The Biffi EHO will maintain the
previous calibrated value.
cF
N/A
Analog Output 2
Calibration Status. Not
Searchable/Configurable
CALIBRATE UPPER LIMIT OF ANALOG
OUTPUT 2
Calibrate the Analog Output 2 Channel
for 20 mA equivalent value. The channel
output needs to be monitored externally.
oU
Yes/No
N/A
ANALOG OUTPUT 2 CALIBRATION CHOICE
Select if the Analog Output 2 needs to be
increased or decreased.
cC
0 = Increment
1 = Decrement
0 = Increment
CALIBRATING ANALOG OUTPUT 2
The Analog Output can be changed based
on selection at [c][C] menu. 'Yes' option
at this menu means accept the output.
'No' option at this menu will increase or
decrease the output.
c2
Yes/No
N/A
CALIBRATION PASSED FOR UPPER LIMIT
(CALIBRATION STATUS)
The Analog Output 1 channel is calibrated
for the desired output.
cU
N/A
Analog Output 2
Calibration Status. Not
Searchable/Configurable
CALIBRATED FAILED (CALIBRATION STATUS)
Calibration for Analog Output 2 channel
has failed. The Biffi EHO will maintain the
previous calibrated value.
cF
N/A
Analog Output 2
Calibration Status. Not
Searchable/Configurable