Installation, Operation and Maintenance Manual
VCIOM-15345-EN Rev. 1
February 2022
25
Start-up Procedure
Section 4: Start-up Procedure
4.4.3
Use the handle supplied with the pump to raise the pump clevis. This will draw
hydraulic fluid from the reservoir (4) into the handpump.
4.4.4
Pull the pump handle down to discharge the hydraulic fluid into the cylinder of the
actuator (1). Repeat until you see the handpump is working correctly.
4.4.5
Repeat operating the handle until the actuator has completed its power stroke.
4.4.6
Push Handpump Bypass Valve (16) located on the bottom of the handpump and
pull the pump handle down, retracting the pump ram back into the pump body.
4.4.7
Slowly open Manual Bypass Valve (19) (Lockable) to allow the actuator to
spring-return to its fail-safe position.
4.4.8
After the actuator has returned to its fail-safe position and pressure has been
released, close Manual Bypass Valve (19) (Lockable).
4.4.9
Open the Handpump Isolation Valves (8) to return to automatic operation.
4.4.10
Check Reservoir (4) to see the hydraulic fluid is at the proper level.
NOTICE
Manual Bypass Valve (Lockable) (19) must be closed to enable any mode of operation.
Handpump Isolation Valve (8) must be open for normal operation.
4.5
Hydraulic Test
The system has been hydrostatic and function tested at the factory before shipping.
This test is to discover if any leaks have developed in the hydraulic fittings during shipment.
4.5.1
Open Handpump Isolation Valve (8) and ensure Manual Bypass Valve (19)
(Lockable) is closed.
4.5.2
Using the supplied handle, stroke Handpump (13) four or five times and stop.
Allow the unit to remain under pressure for a few minutes and check all fittings
for leakage.
4.5.3
If any leakage is found, release the pressure by slowly opening Manual Bypass Valve
(19) (Lockable). Repair any leakage and repeat the pressure test from Section 4.4.1.
4.5.4
Push Handpump Bypass Valve (16), located on the bottom of the handpump, and
pull the pump handle, retracting the pump ram back into the pump body.
4.5.5
Open the Handpump Isolation valves (8). ((See NOTICE above.))
4.5.6
Check Reservoir (4) to see the hydraulic fluid is at the proper level.