February 2022
Installation, Operation and Maintenance Manual
VCIOM-15345-EN Rev. 1
34
Communication Protocols
Section 5: Communication Protocols
Figure 14
Modbus/Multi-drop Topology
5.1.2
Multi-drop Bus Topology
—
Only one data path to each device from network master
—
No short-circuit or ground fault protection in network
—
Open-circuit protection only to the first cable fault
—
No redundancy included
—
Maximum network cable length is only 1200 m (4000 ft)
—
Maximum number of valves in network is 32
—
Repeaters required to extend the network
5.1.3
STC Terminal Connections
Table 6.
STC Pin Connections
STC PIN Connections
Modbus Connections
39
CHA +
40
Shield
41
CHA -
42
Shield
43
CHB +
44
CHB -
Primary Network
Master
RS-232, RS-485, or RS-422 Modbus
RS-485, Modbus, Twisted
Shielded-Pair Cable, 9600 Baud