Installing control panel and external controls
2.7.1 Control panel details
Positioning
•
You may fix the control panel either to the wall or to a
standard socket.
Cabling
Note:
n
Take the following into account, otherwise faults may
occur:
-
The control cable between the control panel and the
(first) connected unit may not be longer than 50 m.
-
Keep control cables away from electromagnetic fields
and interference sources such as high-voltage cables
and fluorescent-light starters.
-
Stretch control cables out or roll them up neatly.
-
Do not remove the dummy plug, unless otherwise
stated.
Note:
n
Use only control cables from Biddle. Standard modular
telephone cable is
not
suitable.
Multiple units operated from one single control panel
•
Up to 10 units can be connected to one single control
panel. To do so, the units must be interlinked.
•
Only units that have the same unit code (see “code” on
the type plate, section
1.3.4
) can be operated from one
control panel at the same time.
•
The total length of the control cables is not to exceed
100 m.
2.7.2 External control details
Control panel input
The control panel has one input signal interface. To this, a
timer or a door switch is usually connected.
Type CA M-150-W-F
Code 1213
U 230 V 1N~ 50 Hz
Biddle bv
Markowei 4
NL-9288 HA Kootstertille
Nº 5426/1-1 00-01
I
max
L1 2.4 A
I
max
L2 -
M 60 kg
I
max
L3 -
Medium LPHW
P
motor
0.56 kW
p
max
1400 kPa
P
heating
-