- 65 -
INST
ALLA
TION
COMMISSIONING
Fig. 7.36
0
2
1
8
1
21
1 5
6
3
9
• Press buttons
and
at the same
time to enter transparent programming (Fig.
7.37).
Fig. 7.37
• Press buttons
or
to display the
"
PM10
" program for selecting the ignition
frequency (Fig. 7.38).
Fig. 7.38
In Fig. 7.38 a SET programmed at
90
is dis-
played corresponding to a re-ignition time of
about 3 minutes.
The adjustment field is from 0 to 8 and half
minutes.
Each step increased or decreased corre-
sponds to 2 seconds.
• To modify the programmed SET, act on but-
tons
or
and wait for the number
programmed to flash (Fig. 7.39).
Fig. 7.39
• To exit programming, press button .
7.13 Checking the ignition device
With the burner on high flame close the gas
cock.
After four ignition attempts (about four min-
utes) the boiler does not function and a code
that alternates between the letter
E
and the
writing
RESET
appear on the LCD display, it
indicates that the safety lock-out has stopped
the boiler. The display background flashes
(Fig. 7.40).
Fig. 7.40
Press the reset key 13 on the boiler control
panel to reset its functioning.