- 70 -
MAINTENANCE
GAS CONVERSION
Fig. 8.3
9
10
11
12 13
14
15
16
17
Fig. 8.4
• Scroll the various parameters using keys
15 or 16 until the letters
P05
are displayed
on the LCD display, indicating that "pa-
rameter 05" (Fig. 8.5) has been activated.
Fig. 8.5
• Pressing the 9 key 5 times it is possible to
modify the value of parameter 5 (see table).
Parameter
Gas type
00
G20
05
G31
• By pressing key 12 (Fig. 8.3) confirmation
of the inserted value is obtained.
• Press keys 15 or 16 (Fig. 8.3) to exit with-
out changing the value.
• Exiting the “programming mode” is au-
tomatic, after 15 minutes, or by cutting
power.
• Calibrate the gas valve according to the
instructions given in the Service manual,
section Gas valve - Adjustment.
• Reposition the controls panel and remount
the front panel of the body.
• Apply the label indicating the gas nature
and pressure value for which the appli-
ance is regulated. The self adhesive label
is contained in the transformation kit.