INSTALLATION MANUAL

ENGLISH

 

associates the required key to 2nd radio channel

-   Read (

read

)

  Checks one key of a receiver; if stored it displays a message showing the re-

ceiver number in the memory location (from 01 to 64), and the key number 

(T1, T2, T3 or T4).

-   Eliminate list  (

erease 64

)

 

WARNING! Completely removes all memorised radio control devices from 

the receiver memory. 

-  Receiver code reading (

RX code

)

 

This displays the code entered in the receiver (par. 11).

Consult paragraphs 8, 9, 10 and 11 for further information concerning the 

advanced functions of the Clonix incorporated receiver.

6.4) LANGUAGE MENU (

language

)

Allows you to set the language on the display programmer.

-   ITALIAN (

ITA

-   FRENCH (

FRA

-   GERMAN (

DEU

)

-   ENGLISH (

ENG

-   SPANISH (

ESP

6.5) DEFAULT MENU (

default

)

Restores the preset default values on the control unit. After restoring, a new 

autoset operation must be carried out. 

  

6.6) DIAGNOSTICS AND MONITORING

The display on the LIBRA-C-MA panel shows some useful information, both 

during normal operation and in the case of malfunctions.

Diagnostics:

In the case of malfunctions, the display shows a message indicating which device 

needs to be checked:

STRT   

=   START input activation

STOP   

=   STOP input activation

PHOT   

=   PHOT input activation

FLT  

 

=  FAULT input activation for checked photocells 

TH   

=  Activation of software thermal protection

ER 1   

=   Board error during safety device check

ER 2   

=   Board error during safety device check

When using traditional limit switches connected to terminals 24-25-26-27:

SWO1 

=  activation of Motor 1 opening limit switch input

SWC1  

=  activation of Motor 1 closing limit switch input

SWO2 

=  activation of Motor 2 opening limit switch input

SWC2  

=  activation of Motor 2 closing limit switch input

In the case where an obstacle is found, the LIBRA-C-MA panel stops the door 

and activates a reverse manoeuvre; at the same time the display shows the 

“AMP” message.

Monitoring:

During the opening and closing phases, the display shows four digits separated by 

a dot, for example 

35.40.

 The digits are constantly updated during the manoeuvre, 

and represent the maximum torque reached by motor 1 (

35

) and motor 2 (

40

).

These values allow the torque setting to be corrected.

If the maximum torque value reached during the manoeuvre gets sensibly close 

to the value set in the parameter menu, malfunctions may occur in the future 

following wear or slight door deformation.

It is therefore advisable to check the maximum torque reached during some of 

the manoeuvres carried out in the course of installation, and if necessary set a 

value about 15-20 percent points higher in the parameter menu.

6.7) ADJUSTING PROCEDURE

-  Before switching on, check electrical connections.

-  Set the following parameters: Automatic Closing Time, Opening and closing 

delay times, Slow-down speed and Zone number.

-  Set all the logics.

-  Carry out the autoset procedure.

After completing the autoset procedure, the Motor fast time and the Torque can 

be manually adjusted.

WARNING! Any incorrect setting can cause injuries to persons and animals 

or damage to things. 

WARNING: Check that the impact force value measured at  

the points established by the EN 12445 standard is lower than that 

specified in the EN 12453 standard.

To obtain a better result, it is advisable to carry out the autoset procedure and 

the fast time setting with the motors at rest (i.e. not overheated by a considerable 

number of consecutive manoeuvres).

6.8) AUTOSET MENU (

autoset

)

Allows you to automatically set the Motor torque. 

WARNING! The autosetting operation is carried out from closing end-of-stroke 

devices. If Autoset is commanded in a different position an error message indi-

cating “

nsvc

” will be displayed and the required manoeuvre will not take place.

WARNING!! The autoset operation is only to be carried out after checking the 

exact leaf (opening/closing) movement, and correct limit-switch activation.

Set the adequate slow-down speed: by pressing OK the message “.... .... ....” is 

displayed and the control unit commands an opening manoeuvre without slow-

down, followed by a closing manoeuvre without slow-down during which the 

duration of the stroke is memorised. Then, the control unit commands a second 

opening manoeuvre with slow-down followed by a second closing manoeuvre 

with slow-down during which the minimum torque value necessary for the 

movement of the leaf is automatically set. 

During this phase, it is important to avoid obscuring the photocells, as well as 

using the START, STOP, PED, CLOS or OPEN commands and the display. 

After completion, if the Autoset was successful, an “OK” message will be displayed 

on the control unit which will then return to the Autoset menu after pressing 

the “OK” key.

If, on the other hand, the control unit displays the “KO” message, it means that 

the autoset procedure has not been successfully completed; it is thus necessary 

to check the wear condition of the gate and the regular movement of the leaves 

before proceeding to a new autoset operation.               

WARNING!  During the autoset phase, the obstacle detection function is not 

active, therefore the installer must control the automation movement and pre-

vent persons and things from approaching or standing within the automation 

working range. 

In the case where buffer batteries are used, autosetting must be carried out with 

the control panel supplied by mains power voltage.

WARNING: The torque values fixed by means of the autoset procedure 

refer to the slow-down speed fixed during the same procedure. If the 

slow-down speed is changed, a new autoset procedure must be carried out.

WARNING: Check that the impact force value measured at the  

points established by the EN 12445 standard is lower than that speci-

fied in the EN 12453 standard.

Incorrect sensitivity setting can cause injuries to persons or  

animals, or damage to things.

7) STATISTICS

Having connected the universal palmtop programmer to the control unit, enter 

the CONTROL UNIT / STATISTICS menu and scroll the screenful showing the 

statistical parameters:

-  Board microprocessor software version.

-  Number of cycles carried out. If motors are replaced, count the number of 

manoeuvres carried out up to that time. 

-  Number of cycles carried out from the latest maintenance operation. 

 

It is automatically set to zero after each self-diagnosis or parameter writ-

ing. 

-  Date of latest maintenance operation. To be updated manually from the ap-

propriate menu “Update maintenance date”.

-  Installation description. 16 characters can be entered for installation identifica-

tion.

8) INTEGRATED RECEIVER TECHNICAL SPECIFICATION

Receiver output channels: 

-  output channel 1, if activated, controls a START command. 

-  output channel 2, if activated, controls the excitation of the 2nd radio channel 

relay for 1s.

Transmitter versions which can be used:

all Rolling Code transmitters compatible with 

.

ANTENNA INSTALLATION

Use an antenna tuned to 433MHz.

For Antenna-Receiver connection, use RG8 coaxial cable.

The presence of metallic masses next to the antenna can interfere with radio 

reception. In case of insufficient transmitter range, move the antenna to a more 

suitable position.

9) RECEIVER CONFIGURATION

The on-board receiver combines characteristics of utmost safety in copying vari-

able code (rolling code) coding with the convenience of carrying out transmitter 

“cloning” operations thanks to an exclusive system.

Cloning a transmitter means creating a transmitter which can be automatically 

included within  the list of the transmitters memorised in the receiver, either as 

an addition or as a replacement of a particular transmitter.

Cloning by replacement is used to create a new transmitter which takes the place 

of the one previously memorised in the receiver; in this way a specific transmitter 

can be removed from the memory and will no longer be usable.

Therefore it will be possible to remotely program a large number of additional 

transmitters or, for example, replacement transmitters for those which have been 

lost, without making changes directly to the receiver. 

When coding safety is not a decisive factor, the on-board receiver allows you to 

carry out fixed-code additional cloning which, although abandoning the variable 

code, provides a high number of coding combinations, therefore keeping it pos-

sible to “copy” any transmitter which has already been programmed.

PROGRAMMING

Transmitter storage can be carried out in manual mode or by means of the uni-

versal palmtop programmer which allows the complete installation database to 

be managed through the Eedbase software.

12 - LIBRA-C-MA 

D811494_07

Summary of Contents for LIBRA-C-MA

Page 1: ...STALLATION INSTALLATIONS UND GEBRAUCHSANLEITUNG INSTRUCCIONES DE USO Y DE INSTALACION INSTRUÇÕES DE USO E DE INSTALAÇÃO D811494 ver 07 18 04 2012 I GB F D E P QUADRO COMANDO CONTROL PANEL CENTRALE DE COMMANDE SELBSTÜBERWACHENDE STEUERUNG CUADRO DE MANDOS QUADRO DE COMANDO LIBRA C MA 8 027908 288554 ...

Page 2: ... lampeggiante in posizione visibile fissare inoltre alla struttura un cartello di Attenzione Fissareinmodopermanenteunaetichettarelativaalfunzionamentodellosblocco manuale dell automazione e apporla vicino all organo di manovra Assicurarsi che durante la manovra siano evitati o protetti i rischi meccanici ed inparticolarel impatto loschiacciamento ilconvogliamento ilcesoiamentotra parte guidata e ...

Page 3: ...BOS BT IGEA BT 9 10 Collegamento lampeggiante 24V 20W max 11 12 Uscita 24V 180mA max alimentazione fotocellule o altri dispositivi 13 14 Uscita24V Vsafe180mAmax alimentazionetrasmettitorifotocellule con verifica Fig 3a 15 16 Pulsante START N O 15 17 Pulsante STOP N C Se non usato lasciare il ponticello 15 17 inserito 15 18 Ingresso Fotocellula N C Se non usato lasciare il ponticello 15 18 inserito...

Page 4: ...test phot OFF Logiche avanzate indirizzo 14 ON Attiva la verifica delle fotocellule OFF Disattiva la verifica delle fotocellule Sedisabilitato OFF inibiscelafunzionediverificadellefotocellule consen tendolaconnnessionedidispositivinondotatidicontattosupplementare verifica Spia cancello aperto o II canale radio SCA 2Ch OFF ON L uscitatraimorsetti21 22vieneconfiguratacomeSpiacancelloaperto il II can...

Page 5: ...perazione di autsettaggio va effettuata solo dopo aver verifi cato l esatto movimento dell anta apertura chiusura ed il corretto intervento dei finecorsa Impostarelavelocitàdirallentamentoadeguata nonappenapremutoilpulsante OK viene visualizzato il messaggio la centrale comanda una manovra di apertura senza rallentamento seguita da una manovra di chiusura senza rallen tamento durante le quali memo...

Page 6: ...le due piazzole P1 Fig B2 NOTA IMPORTANTE CONTRASSEGNARE IL PRIMOTRASMETTITORE MEMO RIZZATO CON IL BOLLINO CHIAVE MASTER Il primo trasmettitore nel caso di programmazione manuale assegna il CODICE CHIAVE DEL RICEVITORE questo codice risulta necessario per poter effettuare la successiva clonazione dei radiotrasmettitori 11 CLONAZIONE DEI RADIOTRASMETTITORI Clonazione con rolling code Clonazione a c...

Page 7: ...LIBRA C MA 7 D811494_07 ...

Page 8: ...8 LIBRA C MA D811494_07 ...

Page 9: ... reached by the public Apply at least one warning light flashing light in a visible position and also attach a Warning sign to the structure Attach a label near the operating device in a permanent fashion with informa tion on how to operate the automated system s manual release Make sure that during operation mechanical risks are avoided or relevant protective measures taken and more specifically ...

Page 10: ...to photocell transmitters with checking function Fig 3a 15 16 START pushbutton N O 15 17 STOP pushbutton N C If not used leave the bridge 15 17 connected 15 18 Photocell input N C If not used leave the bridge 15 18 connected 15 19 Faultinput N O InputforphotocellsprovidedwithcheckingN O contact Fig 3a 15 20 Pedestrian pushbutton input N O Activation is carried out by motor 2 if the opening cycle h...

Page 11: ... devices not provided with additional checking contact Gate open or 2nd radio channel warning light SCA 2ch OFF ON Theoutputbetweenterminals21and22isconfiguredasGate openwarning light in this case the 2nd radio channel controls pedestrian opening OFF The output between terminals 21 and 22 is configured as 2nd radio chan nel Motors in operation 1 mot ON OFF ON Only motor 2 is in operation terminals...

Page 12: ...cond opening manoeuvre with slow down followed by a second closing manoeuvre with slow down during which the minimum torque value necessary for the movement of the leaf is automatically set During this phase it is important to avoid obscuring the photocells as well as using the START STOP PED CLOS or OPEN commands and the display Aftercompletion iftheAutosetwassuccessful an OK messagewillbedisplay...

Page 13: ...oning of the radio transmitters 11 RADIO TRANSMITTER CLONING Rolling code cloning Fixed code cloning MakereferencetotheuniversalpalmtopprogrammerInstructionsandtheCLONIX Programming Guide 11 1 ADVANCED PROGRAMMING COLLECTIVE RECEIVERS MakereferencetotheuniversalpalmtopprogrammerInstructionsandtheCLONIX Programming Guide 12 SERIAL CONNECTION USING SCS1 BOARD Fig 6 TheLIBRA C MAcontrolpanelallowssev...

Page 14: ...14 LIBRA C MA D811494_07 ...

Page 15: ...LIBRA C MA 15 D811494_07 ...

Page 16: ...ivement des pièces détachées originales pour les opérations d entretien ou les réparations Le Fabricant décline toute responsabilité quant à la sécurité et au bon fonctionnement de l automatisation en cas d utilisation de composants d autres Fabricants Ne modifier d aucune façon les composants de l automatisation sans l autorisa tion expresse du Fabricant Informer l utilisateur de l installation s...

Page 17: ...n feu clignotant 24V 20W maxi 11 12 Sortie 24V 180mA maxi alimentation cellules photoélectriques ou autres dispositifs 13 14 Sortie 24V V safe 180mA maxi alimentation émetteurs cellules photoélectriques avec vérification Fig 3a 15 16 Touche START N O 15 17 Touche STOP N F Si elle n est pas utilisée il faut laisser le shunt 15 17 inséré 15 18 Entrée Cellule photoélectrique N F Si elle n est pas uti...

Page 18: ...et d ajouter une touche d une commande radio dans la mémoire du récepteur après la mémorisation il affiche le numéro du récepteur dans l emplacement de la mémoire 01 à 64 Ajouter Touche start adj start associe la touche désirée à la commande Start Ajouter Touche 2ch adj 2ch associe la touche désirée à la commande 2 canal radio Couple moteur 1 couple mot1 50 Paramètres ultérieurs adresse 3 Introdui...

Page 19: ...ie par une manœuvre de fermeture sans ralentissement pendantlesquellesellemémoriseladuréedelacourse ensuite la centralecommandeunedeuxièmemanœuvredeouvertureavecralentissement suivie par une deuxième manœuvre de fermeture avec ralentissement pendant lesquelles la valeur minimale de couple nécessaire au mouvement du vantail est automatiquement instaurée Pendant cette phase il est important d éviter...

Page 20: ... cas de programmation manuelle attribue le code clé au récepteur ce code est nécessaire pour pouvoir effectuer le clonage successif des émetteurs radio 11 CLONAGE DES RADIOÉMETTEURS Clonage avec rolling code Clonage à code fixe Se référer aux instructions de programmateur de poche universel et au Guide de programmation CLONIX 11 1 PROGRAMMATION AVANCÉE COMMUNAUTÉ DE RÉCEPTEURS Se référer aux instr...

Page 21: ...LIBRA C MA 21 D811494_07 ...

Page 22: ...22 LIBRA C MA D811494_07 ...

Page 23: ...rung richtig eingestellt worden ist und dass die Schutzsysteme den Betrieb ordnungsgemäß blockieren Verwenden Sie bei allen Wartungs und Reparaturarbeiten ausschließlich Originaler satzteile Die Firma haftet nicht für die Sicherheit und den ordnungsgemäßen Betrieb der Automatik falls Komponenten von anderen Herstellern verwendet werden Nehmen Sie keine Änderungen an den Komponenten der Automatik v...

Page 24: ...g Lichtschrankensender mit Selbstüberwachung Abb 3a 15 16 Eingang START N O 15 17 Eingang STOP N C Falls nicht genutzt überbrückt 15 17 lassen 15 18 Eingang Lichtschranke N C Falls nicht genutzt überbrückt 15 18 lassen 15 19 Eingang Fault N O Eingang für Lichtschranken mit Prüfkontakt N O Abb 3a Falls nicht genutzt überbrückt lassen 15 20 Eingang Knopf Fußgängerfunktion N O Angesteuert wird Motor ...

Page 25: ...tzlichen Prüfkontakt haben Kontrollampe Tor offen oder 2 Funkkanal SCA 2ch OFF ON Der Ausgang zwischen den Klemmkontakten 21 22 wird als Kontrollampe zur Anzeige derToröffnung konfiguriert der 2 Funkkanal steuert in diesem Fall die Fußgängeröffnung OFF Der Ausgang zwischen den Klemmkontakten 21 22 wird als 2 Funkkanal konfiguriert Anzahl aktive Motoren 1 mot activ OFF ON Nur Motor 2 ist zugeschalt...

Page 26: ...ne Verlangsamung WährenddieserVorgängewirddieHubdauergespeichert Danach veranlaßt die Steuerung einen zweiten Öffnungsvorgang mit Verlangsamung gefolgt von einem zweiten Schließvorgang mit Verlangsamung Während dieser Vorgänge wird automatisch das Drehmoment eingestellt das für die Flügelbewe gung mindestens erforderlich ist Während dieser Phase ist es wichtig daß die Lichtschranke nicht verdunkel...

Page 27: ...ste Sender weist bei der manuellen Programmierung dem Empfänger den Schlüsselcode zu dieser Code ist erforderlich um anschließend die Funksender klonieren zu können 11 KLONIERUNG DER FUNKSENDER Klonierung mit Rollcode Klonierung mit Festcode SiehehierzudieBetriebsanleitunguniversellenpalmtop programmiererunddie Programmieranleitung CLONIX 11 1 FORTGESCHRITTENE PROGRAMMIERUNG EMPFÄNGERKOLLEKTIV Sie...

Page 28: ...28 LIBRA C MA D811494_07 ...

Page 29: ...LIBRA C MA 29 D811494_07 ...

Page 30: ...ar exclusivamente piezas originales para todas las operaciones de manteni miento y reparación La Empresa no se responsabiliza de la seguridad y el buen funcionamiento de la automatización en caso que se utilicen componentes de otros fabricantes No realizar ninguna modificación a los componentes de la automatización si no se cuenta con autorización expresa por parte de la Empresa Instruir al usuari...

Page 31: ...fotocélulas con control Fig 3a 15 16 Botón START N O 15 17 Botón STOP N C Si no se utiliza déjese puenteado 15 17 15 18 Entrada Fotocélula N C Si no se utiliza déjese puenteado 15 18 15 19 Entrada Fault N O Entrada para fotocélulas dotadas de contacto N O de control Fig 3a 15 20 Entrada botón peatonal N O El accionamiento se produce en el motor 2 Sielciclodeaperturayahaempezado nocomopeatonal elco...

Page 32: ...es 21 22 se configura como II canal radio Motores en función 1 Mot activ OFF ON Resulta en función exclusivamente el motor 2 bornes 3 4 5 Con esta configuración la entrada peatonal resulta inhabilitada OFF Los dos motores están en función Mantenimiento del bloqueo Manten bloqueo OFF Fig 5 ON Debe utilizarse en presencia de retén mecánico de cierre Esta función activa la presión de las hojas sobre ...

Page 33: ...o de las fotocélulas así como la utilización de los mandos START STOP PED CLOS OPEN y del display Al final si la configuración automática se ha realizado con éxito en la central de mando se visualiza el mensaje OK y una vez presionada la tecla OK se vuelve al menú de Configuración automática Si en cambio la central visualiza el mensaje Prog KO significa que el procedi mientodeconfiguraciónautomáti...

Page 34: ...ORES Clonación con rolling code Clonación con código fijo Se remite a las instrucciones del programador de bolsillo universal y a la Guía de programación CLONIX 11 1 PROGRAMACION AVANZADA COMUNIDAD DE RECEPTORES Se remite a las instrucciones del programador de bolsillo universal y a la Guía de programación CLONIX 12 CONEXION SERIAL CON SCS1 Fig 6 El cuadro de mandos LIBRA C MA permite mediante ent...

Page 35: ...LIBRA C MA 35 D811494_07 ...

Page 36: ...36 LIBRA C MA D811494_07 ...

Page 37: ...Atenção na estrutura Fixarpermanentementeumaetiquetarelativaaofuncionamentododesbloqueio manual do automatismo e colocá la perto do órgão de manobra Acertar se de que durante a manobra sejam evitados ou protegidos os riscos mecânicos e em especial o esmagamento o arrastamento a tesourada entre a parte guiada e as partes circunstantes Depoisdeterefectuadoainstalação acertar sedequeoajustedoautomati...

Page 38: ...dores com gestão do fim de curso com 1 único fio PHOBOS BT IGEA BT 9 10 Conexão lampejante 24V 20W máx 11 12 Saída 24V 180mA máx alimentação fotocélulas ou outros disposi tivos 13 14 Saída24V Vsafe180mAmáx alimentaçãotransmissoresfotocélulas com verificação Fig 3a 15 16 Botão START N A 15 17 Botão STOP N F Se não for usada deixar a ponte 15 17 ligada 15 18 EntradaFotocélula N F Senãoforusada deixa...

Page 39: ...las Se desactivado inibe a função de verificação das fotocélulas consentindo a ligação de dispositivos não equipados de contacto suplementar de veri ficação Indicador luminoso de portão aberto ou II canal rádio SCA 2ch OFF ON A saída entre os bornes 21 22 é configurada como Indicador luminoso de portão aberto nestecaso oII canalrádiocomandaaaberturadopostigo OFF A saída entre os bornes 21 22 é con...

Page 40: ...AMAÇÃO O armazenamento dos transmissores pode ser efectuado em modo manual ou por meio do programador palmar universal que consente a gestão através do software EEdbase do database completo da instalação Neste último caso a programação do receptor executa se através da conexão de programador palmar universal ao quadro de comando LIBRA C MA utilizando efectuaumaverificaçãodeumatecladeumreceptor sea...

Page 41: ...o dos radiotransmissores 11 CLONAÇÃO DOS RADIOTRANSMISSORES Clonação com rolling code Clonação com código fixo Fazer referência às instruções programador palmar universal e à Guia de pro gramação CLONIX 11 1 PROGRAMAÇÃO AVANÇADA COMUNIDADE DE RECEPTORES Fazer referência às instruções de programador palmar universal e à Guia de programação CLONIX 12 CONEXÃO SÉRIE Fig 6 O quadro de comando LIBRA C M...

Page 42: ...42 LIBRA C MA D811494_07 ...

Page 43: ...LIBRA C MA 43 D811494_07 ...

Page 44: ... SCA 22 19 20 21 22 24 V Controllo finecorsa negli attuatori con gestione finecorsa con 1 solo filo PHOBOS BT IGEA BT Limit switch control for actuators with limit switch control by means of 1 wire only PHOBOS BT IGEA BT C o n t r ô l e f i n d e c o u r s e d a n s l e s actionneurs avec gestion de fin de course avec un seul fil PHOBOS BT IGEA BT Endschalter Kontrolle in Antrieben mit 1 Draht End...

Page 45: ... 2 1 2 3 4 P1 T1 Led T2 P1 P1 T1 T2 T3 T4 P1 P1 T1 T2 T3 T4 UNIPOWER UNIFLAT UNIFLAT UNIMITTO UNITRC UNIMITTO UNITRC COM 11 12 13 14 15 16 17 18 19 20 PHOT FAULT 24V 24V 24V VSafe 24V VSafe 13 14 13 14 18 15 1 SCS1 MA 3 SCS1 MA 2 SCS1 MA 12 11 12 11 15 19 12 11 Rx 2 Rx 1 Tx 2 Tx 1 1 2 3 4 5 1 2 1 2 1 2 3 4 13 14 Rx 3 Tx 3 5 5 1 2 1 2 3 4 SCS1 MA 1 2 3 4 5 6 COM 11 12 13 14 15 16 17 18 19 20 PHOT F...

Page 46: ...46 LIBRA C MA D811494_07 ...

Page 47: ...LIBRA C MA 47 D811494_07 ...

Page 48: ......

Reviews: