background image

INSTALLATION MANUAL

ENGLISH

 

(Advanced parameters 

 address 4)

 

Set the numerical value of the motor 2 torque between 1% and 99%.

-   Motor 1 slow-down torque (

m1 t slow

) [ 45% ] 

 

(Advanced parameters 

 address 8)

  Set the numerical value for slow-down torque of motor 1 between 1% and 

99%.

-   Motor 2 slow-down torque (

m2 t slow

)  [ 45% ]

  (Advanced parameters 

 address 9)

  Set the numerical value for slow-down torque of motor 2 between 1% and 

99%.

  NOTE: In case of obstacle detection, the Ampere-stop function halts the 

leaf movement, reverses its motion for 1 sec. and then halts in the STOP 

status.

WARNING: Check that the impact force value measured at  

the points established by the EN 12445 standard is lower than that 

specified in the EN 12453 standard.

Incorrect sensitivity setting can cause injuries to persons or  

animals, or damage to things.

-   Opening delay time (

open delay time

) [ 1s ]

 

Set the opening delay time for motor 1 relative to motor 2, between 1 and 10 

seconds. 

-   Closing delay time (

cls delay time

) [ 1s ]

 

Set the closing delay time for motor 2 relative to motor 1, between 1 and 25 

seconds.

-   Motor 1 fast time (

m1 fast time

) [ 15s ]

  (Advanced parameters 

 address 6)

 

Set the time to normal speed (not slowed down), ranging from 1 to 30 seconds. 

Carry out the settings from the gate-closed position; if settings are carried 

out from a different point, they will become effective as from the subsequent 

opening manoeuvre.

-   Motor 2 fast time (

m2 fast time

) [ 15s ]

  (Advanced parameters 

 address 7)

 

Set the time to normal speed (not slowed down), ranging from 1 to 30 seconds. 

Carry out the settings from the gate-closed position; if settings are carried 

out from a different point, they will become effective as from the subsequent 

opening manoeuvre.

 

Note: The slow-down time, on closing and on opening, is obtained by timing 

one manoeuvre and setting a minimum value for this parameter. If, for example, 

one manoeuvre lasts 25 seconds, a setting of “normal speed time” to 20s will 

produce a slow-down time of 5s both on closing and on opening. 

-  Slow-down speed (

slov speed

) [ 50% ]

  (Advanced parameters 

 address 5)

 

Set the slow-down speed:

 

Sets the slow-down speed percentage between 0% and 99% of normal spe-

ed.

 

0 – slow-down disabled (always fast).

-   Zone (

zone

) [ 0 ] 

  Set the zone number between a minimum value of 0 and a maximum value 

of 127. See paragraph 7 on “Serial connection”.

6.2) LOGIC MENU (

logic.

)

- TCA  (

TCA

) [ OFF ]

ON :  Activates automatic closing

OFF: Excludes automatic closing 

- 3 Steps  (

3 step

)  [ OFF ]

ON:  Enables 3-step logic. A Start impulse has the following effects:

 

door closed: ...........................................................................................................................

opens .......................................................................................................................................

on opening: ....................................................stops and enters TCA (if configured)

 

door open:  ................................................................................................................closes

 

on closing:.........................................................................................stops and reopens

OFF:  Enables 4-step logic. A Start impulse has the following effects:

 

door closed: .............................................................................................................. opens

 

on opening: ....................................................stops and enters TCA (if configured)

 

door open:  ................................................................................................................closes 

 

on closing:...................................................... stops and does not enter TCA (stop)

 

after stopping: ......................................................................................................... opens

- Impulse lock (

ibl open

) [ OFF ]

ON :  The Start impulse has no effect during the opening phase.

OFF:  The Start impulse becomes effective during the opening or closing phase. 

- Rapid closing (

fast cls

) [ OFF ]

ON:  Closes the gate after 3 seconds from photocell disengagement before 

waiting for the end of the TCA set.

OFF:  Command not entered. 

- Photocells on opening (

photc. open

) [ OFF ]

 

(Advanced logics 

 address 14) 

ON:   In case of obscuring, this excludes photocell operation on opening. During 

the closing phase, it immediately reverses the motion.

OFF: In case of obscuring, the photocells are active both on opening and on 

closing. When a photocell is obscured on closing, it reverses the motion 

only after the photocell is disengaged. 

- Photocell test (

test phot

) [ OFF ] 

ON:  Activates photocell check 

OFF:  Deactivates photocell check 

 

If this setting is not activated (OFF), it inhibits the photocell checking func-

tion, allowing connection of devices not provided with additional checking 

contact. 

- Gate-open or 2nd radio channel warning light (

SCA 2ch

) [ OFF ]

ON:  The output between terminals 21 and 22 is configured as Gate-open warning 

light, in this case the 2nd radio channel controls pedestrian opening.

OFF:  The output between terminals 21 and 22 is configured as 2nd radio chan-

nel.

- Motors in operation (

1 mot ON

)  [ OFF ]

ON:  Only motor 2 is in operation (terminals 3, 4 and 5).

 

With this configuration, the pedestrian input is disabled.

OFF:  Both motors are in operation.

- Lock hold (

block persist

) [ OFF ] (Fig. 5)

ON:  To be used when the mechanical closing backstop is fitted.

 

This function activates leaf pressure on the mechanical backstop, without 

this being considered as an obstacle by the Ampere-stop sensor.

 

Therefore the rod continues its travel for another 0.5 sec. after detecting 

the closing limit switch or upon reaching the mechanical backstop. So by 

activating the closing limit switches slightly earlier, the leaves will come to 

a perfect halt against the backstop.  (Fig. 5a)

OFF:  To be used when no mechanical closing backstop is fitted.

 

Movement is exclusively halted by activation of the closing limit switches; in 

this case proceed to carrying out precise setting of the closing limit-switch 

activation. (Fig. 5b) 

- Hold-to-run control (

hold-to-run

) [ OFF ]

ON:  Hold-to-run operation: the manoeuvre continues as long as the control key 

is kept pressed.

 WARNING!: 

Enabling the Hold-to-run logic entails a different use of the 

START and PEDESTRIAN buttons:

 

START 

 

 

takes on the hold-to-run OPEN function

 

PEDESTRIAN    takes on the hold-to-run CLOSE function

OFF:Impulse operation, according to the 3 or 4 step logic.

- Fixed code (

fixed code

) [ OFF ]

 

(Advanced logics 

 address 13)

ON:  The receiver is configured for operation in fixed-code mode, see paragraph 

on “Radio Transmitter Cloning”.

OFF:  The receiver is configured for operation in rolling-code mode, see paragraph 

on “Radio Transmitter Cloning”.

- Radio transmitter programming  (

radio prog

) [ ON ]

 

(Advanced logics 

 address 15)

ON:  This enables transmitter storage via radio:

 

1 – First press the hidden key (P1) and then the normal key (T1, T2, T3 or 

T4) of a transmitter already  memorised in standard mode by means of the 

radio menu.

 

2 – Within 10s press the hidden key (P1) and the normal key (T1, T2, T3 or 

T4) of a transmitter to be memorised.

 

The receiver exits the programming mode after 10s, other new transmitters 

can be entered before the end of this time. 

 

This mode does not require access to the control panel.

OFF:  This disables transmitter storage via radio.

 

The transmitters can only be memorised using the appropriate Radio 

menu.

- Master/Slave  (

Master

) [ OFF ]

ON:  The control panel is set as Master in a centralised connection (see Paragraph 

7). 

OFF:  The control panel is set as Slave in a centralised connection (see Paragraph 

7).

- Start-Open selection (

start - open

) [ OFF ]

ON:  The input between the two terminals 15-16  acts as open. For closing, wait 

until the TCA, which has to be previously enabled, has elapsed.

OFF:  The input between the two terminals 15-16  acts as start.

- Prealarm  (

pre-alarm

) [ OFF ]

ON:  The blinker comes on 3 sec. before the motors start.

OFF: The blinker comes on at the same time as the motors start.

- Automatic fast time  (

auto fast time

) [ ON ]

ON:  The control unit automatically calculates slow-down time and offsets fast time 

to keep slow-down time constant. With this function active, the fast time value 

is continually updated (it is therefore possible to find a setting other than the 

one actually carried out).

OFF:  The control unit does not offset fast time, but applies the preset «fast time» 

parameter, independently of any environmental changes.

6.3) RADIO MENU (

RADIO

)

-   Add 

 

Allows you to add one key of a radio control device to the receiver memory; 

after storage it displays a message showing the receiver number in the memory 

location (from 01 to 64).

 

Add Start button  (

add start

)

 

associates the required key to Start command

 

Add 2ch button (

add 2ch

)

LIBRA-C-MA -  11

D811494_07

Summary of Contents for LIBRA-C-MA

Page 1: ...STALLATION INSTALLATIONS UND GEBRAUCHSANLEITUNG INSTRUCCIONES DE USO Y DE INSTALACION INSTRUÇÕES DE USO E DE INSTALAÇÃO D811494 ver 07 18 04 2012 I GB F D E P QUADRO COMANDO CONTROL PANEL CENTRALE DE COMMANDE SELBSTÜBERWACHENDE STEUERUNG CUADRO DE MANDOS QUADRO DE COMANDO LIBRA C MA 8 027908 288554 ...

Page 2: ... lampeggiante in posizione visibile fissare inoltre alla struttura un cartello di Attenzione Fissareinmodopermanenteunaetichettarelativaalfunzionamentodellosblocco manuale dell automazione e apporla vicino all organo di manovra Assicurarsi che durante la manovra siano evitati o protetti i rischi meccanici ed inparticolarel impatto loschiacciamento ilconvogliamento ilcesoiamentotra parte guidata e ...

Page 3: ...BOS BT IGEA BT 9 10 Collegamento lampeggiante 24V 20W max 11 12 Uscita 24V 180mA max alimentazione fotocellule o altri dispositivi 13 14 Uscita24V Vsafe180mAmax alimentazionetrasmettitorifotocellule con verifica Fig 3a 15 16 Pulsante START N O 15 17 Pulsante STOP N C Se non usato lasciare il ponticello 15 17 inserito 15 18 Ingresso Fotocellula N C Se non usato lasciare il ponticello 15 18 inserito...

Page 4: ...test phot OFF Logiche avanzate indirizzo 14 ON Attiva la verifica delle fotocellule OFF Disattiva la verifica delle fotocellule Sedisabilitato OFF inibiscelafunzionediverificadellefotocellule consen tendolaconnnessionedidispositivinondotatidicontattosupplementare verifica Spia cancello aperto o II canale radio SCA 2Ch OFF ON L uscitatraimorsetti21 22vieneconfiguratacomeSpiacancelloaperto il II can...

Page 5: ...perazione di autsettaggio va effettuata solo dopo aver verifi cato l esatto movimento dell anta apertura chiusura ed il corretto intervento dei finecorsa Impostarelavelocitàdirallentamentoadeguata nonappenapremutoilpulsante OK viene visualizzato il messaggio la centrale comanda una manovra di apertura senza rallentamento seguita da una manovra di chiusura senza rallen tamento durante le quali memo...

Page 6: ...le due piazzole P1 Fig B2 NOTA IMPORTANTE CONTRASSEGNARE IL PRIMOTRASMETTITORE MEMO RIZZATO CON IL BOLLINO CHIAVE MASTER Il primo trasmettitore nel caso di programmazione manuale assegna il CODICE CHIAVE DEL RICEVITORE questo codice risulta necessario per poter effettuare la successiva clonazione dei radiotrasmettitori 11 CLONAZIONE DEI RADIOTRASMETTITORI Clonazione con rolling code Clonazione a c...

Page 7: ...LIBRA C MA 7 D811494_07 ...

Page 8: ...8 LIBRA C MA D811494_07 ...

Page 9: ... reached by the public Apply at least one warning light flashing light in a visible position and also attach a Warning sign to the structure Attach a label near the operating device in a permanent fashion with informa tion on how to operate the automated system s manual release Make sure that during operation mechanical risks are avoided or relevant protective measures taken and more specifically ...

Page 10: ...to photocell transmitters with checking function Fig 3a 15 16 START pushbutton N O 15 17 STOP pushbutton N C If not used leave the bridge 15 17 connected 15 18 Photocell input N C If not used leave the bridge 15 18 connected 15 19 Faultinput N O InputforphotocellsprovidedwithcheckingN O contact Fig 3a 15 20 Pedestrian pushbutton input N O Activation is carried out by motor 2 if the opening cycle h...

Page 11: ... devices not provided with additional checking contact Gate open or 2nd radio channel warning light SCA 2ch OFF ON Theoutputbetweenterminals21and22isconfiguredasGate openwarning light in this case the 2nd radio channel controls pedestrian opening OFF The output between terminals 21 and 22 is configured as 2nd radio chan nel Motors in operation 1 mot ON OFF ON Only motor 2 is in operation terminals...

Page 12: ...cond opening manoeuvre with slow down followed by a second closing manoeuvre with slow down during which the minimum torque value necessary for the movement of the leaf is automatically set During this phase it is important to avoid obscuring the photocells as well as using the START STOP PED CLOS or OPEN commands and the display Aftercompletion iftheAutosetwassuccessful an OK messagewillbedisplay...

Page 13: ...oning of the radio transmitters 11 RADIO TRANSMITTER CLONING Rolling code cloning Fixed code cloning MakereferencetotheuniversalpalmtopprogrammerInstructionsandtheCLONIX Programming Guide 11 1 ADVANCED PROGRAMMING COLLECTIVE RECEIVERS MakereferencetotheuniversalpalmtopprogrammerInstructionsandtheCLONIX Programming Guide 12 SERIAL CONNECTION USING SCS1 BOARD Fig 6 TheLIBRA C MAcontrolpanelallowssev...

Page 14: ...14 LIBRA C MA D811494_07 ...

Page 15: ...LIBRA C MA 15 D811494_07 ...

Page 16: ...ivement des pièces détachées originales pour les opérations d entretien ou les réparations Le Fabricant décline toute responsabilité quant à la sécurité et au bon fonctionnement de l automatisation en cas d utilisation de composants d autres Fabricants Ne modifier d aucune façon les composants de l automatisation sans l autorisa tion expresse du Fabricant Informer l utilisateur de l installation s...

Page 17: ...n feu clignotant 24V 20W maxi 11 12 Sortie 24V 180mA maxi alimentation cellules photoélectriques ou autres dispositifs 13 14 Sortie 24V V safe 180mA maxi alimentation émetteurs cellules photoélectriques avec vérification Fig 3a 15 16 Touche START N O 15 17 Touche STOP N F Si elle n est pas utilisée il faut laisser le shunt 15 17 inséré 15 18 Entrée Cellule photoélectrique N F Si elle n est pas uti...

Page 18: ...et d ajouter une touche d une commande radio dans la mémoire du récepteur après la mémorisation il affiche le numéro du récepteur dans l emplacement de la mémoire 01 à 64 Ajouter Touche start adj start associe la touche désirée à la commande Start Ajouter Touche 2ch adj 2ch associe la touche désirée à la commande 2 canal radio Couple moteur 1 couple mot1 50 Paramètres ultérieurs adresse 3 Introdui...

Page 19: ...ie par une manœuvre de fermeture sans ralentissement pendantlesquellesellemémoriseladuréedelacourse ensuite la centralecommandeunedeuxièmemanœuvredeouvertureavecralentissement suivie par une deuxième manœuvre de fermeture avec ralentissement pendant lesquelles la valeur minimale de couple nécessaire au mouvement du vantail est automatiquement instaurée Pendant cette phase il est important d éviter...

Page 20: ... cas de programmation manuelle attribue le code clé au récepteur ce code est nécessaire pour pouvoir effectuer le clonage successif des émetteurs radio 11 CLONAGE DES RADIOÉMETTEURS Clonage avec rolling code Clonage à code fixe Se référer aux instructions de programmateur de poche universel et au Guide de programmation CLONIX 11 1 PROGRAMMATION AVANCÉE COMMUNAUTÉ DE RÉCEPTEURS Se référer aux instr...

Page 21: ...LIBRA C MA 21 D811494_07 ...

Page 22: ...22 LIBRA C MA D811494_07 ...

Page 23: ...rung richtig eingestellt worden ist und dass die Schutzsysteme den Betrieb ordnungsgemäß blockieren Verwenden Sie bei allen Wartungs und Reparaturarbeiten ausschließlich Originaler satzteile Die Firma haftet nicht für die Sicherheit und den ordnungsgemäßen Betrieb der Automatik falls Komponenten von anderen Herstellern verwendet werden Nehmen Sie keine Änderungen an den Komponenten der Automatik v...

Page 24: ...g Lichtschrankensender mit Selbstüberwachung Abb 3a 15 16 Eingang START N O 15 17 Eingang STOP N C Falls nicht genutzt überbrückt 15 17 lassen 15 18 Eingang Lichtschranke N C Falls nicht genutzt überbrückt 15 18 lassen 15 19 Eingang Fault N O Eingang für Lichtschranken mit Prüfkontakt N O Abb 3a Falls nicht genutzt überbrückt lassen 15 20 Eingang Knopf Fußgängerfunktion N O Angesteuert wird Motor ...

Page 25: ...tzlichen Prüfkontakt haben Kontrollampe Tor offen oder 2 Funkkanal SCA 2ch OFF ON Der Ausgang zwischen den Klemmkontakten 21 22 wird als Kontrollampe zur Anzeige derToröffnung konfiguriert der 2 Funkkanal steuert in diesem Fall die Fußgängeröffnung OFF Der Ausgang zwischen den Klemmkontakten 21 22 wird als 2 Funkkanal konfiguriert Anzahl aktive Motoren 1 mot activ OFF ON Nur Motor 2 ist zugeschalt...

Page 26: ...ne Verlangsamung WährenddieserVorgängewirddieHubdauergespeichert Danach veranlaßt die Steuerung einen zweiten Öffnungsvorgang mit Verlangsamung gefolgt von einem zweiten Schließvorgang mit Verlangsamung Während dieser Vorgänge wird automatisch das Drehmoment eingestellt das für die Flügelbewe gung mindestens erforderlich ist Während dieser Phase ist es wichtig daß die Lichtschranke nicht verdunkel...

Page 27: ...ste Sender weist bei der manuellen Programmierung dem Empfänger den Schlüsselcode zu dieser Code ist erforderlich um anschließend die Funksender klonieren zu können 11 KLONIERUNG DER FUNKSENDER Klonierung mit Rollcode Klonierung mit Festcode SiehehierzudieBetriebsanleitunguniversellenpalmtop programmiererunddie Programmieranleitung CLONIX 11 1 FORTGESCHRITTENE PROGRAMMIERUNG EMPFÄNGERKOLLEKTIV Sie...

Page 28: ...28 LIBRA C MA D811494_07 ...

Page 29: ...LIBRA C MA 29 D811494_07 ...

Page 30: ...ar exclusivamente piezas originales para todas las operaciones de manteni miento y reparación La Empresa no se responsabiliza de la seguridad y el buen funcionamiento de la automatización en caso que se utilicen componentes de otros fabricantes No realizar ninguna modificación a los componentes de la automatización si no se cuenta con autorización expresa por parte de la Empresa Instruir al usuari...

Page 31: ...fotocélulas con control Fig 3a 15 16 Botón START N O 15 17 Botón STOP N C Si no se utiliza déjese puenteado 15 17 15 18 Entrada Fotocélula N C Si no se utiliza déjese puenteado 15 18 15 19 Entrada Fault N O Entrada para fotocélulas dotadas de contacto N O de control Fig 3a 15 20 Entrada botón peatonal N O El accionamiento se produce en el motor 2 Sielciclodeaperturayahaempezado nocomopeatonal elco...

Page 32: ...es 21 22 se configura como II canal radio Motores en función 1 Mot activ OFF ON Resulta en función exclusivamente el motor 2 bornes 3 4 5 Con esta configuración la entrada peatonal resulta inhabilitada OFF Los dos motores están en función Mantenimiento del bloqueo Manten bloqueo OFF Fig 5 ON Debe utilizarse en presencia de retén mecánico de cierre Esta función activa la presión de las hojas sobre ...

Page 33: ...o de las fotocélulas así como la utilización de los mandos START STOP PED CLOS OPEN y del display Al final si la configuración automática se ha realizado con éxito en la central de mando se visualiza el mensaje OK y una vez presionada la tecla OK se vuelve al menú de Configuración automática Si en cambio la central visualiza el mensaje Prog KO significa que el procedi mientodeconfiguraciónautomáti...

Page 34: ...ORES Clonación con rolling code Clonación con código fijo Se remite a las instrucciones del programador de bolsillo universal y a la Guía de programación CLONIX 11 1 PROGRAMACION AVANZADA COMUNIDAD DE RECEPTORES Se remite a las instrucciones del programador de bolsillo universal y a la Guía de programación CLONIX 12 CONEXION SERIAL CON SCS1 Fig 6 El cuadro de mandos LIBRA C MA permite mediante ent...

Page 35: ...LIBRA C MA 35 D811494_07 ...

Page 36: ...36 LIBRA C MA D811494_07 ...

Page 37: ...Atenção na estrutura Fixarpermanentementeumaetiquetarelativaaofuncionamentododesbloqueio manual do automatismo e colocá la perto do órgão de manobra Acertar se de que durante a manobra sejam evitados ou protegidos os riscos mecânicos e em especial o esmagamento o arrastamento a tesourada entre a parte guiada e as partes circunstantes Depoisdeterefectuadoainstalação acertar sedequeoajustedoautomati...

Page 38: ...dores com gestão do fim de curso com 1 único fio PHOBOS BT IGEA BT 9 10 Conexão lampejante 24V 20W máx 11 12 Saída 24V 180mA máx alimentação fotocélulas ou outros disposi tivos 13 14 Saída24V Vsafe180mAmáx alimentaçãotransmissoresfotocélulas com verificação Fig 3a 15 16 Botão START N A 15 17 Botão STOP N F Se não for usada deixar a ponte 15 17 ligada 15 18 EntradaFotocélula N F Senãoforusada deixa...

Page 39: ...las Se desactivado inibe a função de verificação das fotocélulas consentindo a ligação de dispositivos não equipados de contacto suplementar de veri ficação Indicador luminoso de portão aberto ou II canal rádio SCA 2ch OFF ON A saída entre os bornes 21 22 é configurada como Indicador luminoso de portão aberto nestecaso oII canalrádiocomandaaaberturadopostigo OFF A saída entre os bornes 21 22 é con...

Page 40: ...AMAÇÃO O armazenamento dos transmissores pode ser efectuado em modo manual ou por meio do programador palmar universal que consente a gestão através do software EEdbase do database completo da instalação Neste último caso a programação do receptor executa se através da conexão de programador palmar universal ao quadro de comando LIBRA C MA utilizando efectuaumaverificaçãodeumatecladeumreceptor sea...

Page 41: ...o dos radiotransmissores 11 CLONAÇÃO DOS RADIOTRANSMISSORES Clonação com rolling code Clonação com código fixo Fazer referência às instruções programador palmar universal e à Guia de pro gramação CLONIX 11 1 PROGRAMAÇÃO AVANÇADA COMUNIDADE DE RECEPTORES Fazer referência às instruções de programador palmar universal e à Guia de programação CLONIX 12 CONEXÃO SÉRIE Fig 6 O quadro de comando LIBRA C M...

Page 42: ...42 LIBRA C MA D811494_07 ...

Page 43: ...LIBRA C MA 43 D811494_07 ...

Page 44: ... SCA 22 19 20 21 22 24 V Controllo finecorsa negli attuatori con gestione finecorsa con 1 solo filo PHOBOS BT IGEA BT Limit switch control for actuators with limit switch control by means of 1 wire only PHOBOS BT IGEA BT C o n t r ô l e f i n d e c o u r s e d a n s l e s actionneurs avec gestion de fin de course avec un seul fil PHOBOS BT IGEA BT Endschalter Kontrolle in Antrieben mit 1 Draht End...

Page 45: ... 2 1 2 3 4 P1 T1 Led T2 P1 P1 T1 T2 T3 T4 P1 P1 T1 T2 T3 T4 UNIPOWER UNIFLAT UNIFLAT UNIMITTO UNITRC UNIMITTO UNITRC COM 11 12 13 14 15 16 17 18 19 20 PHOT FAULT 24V 24V 24V VSafe 24V VSafe 13 14 13 14 18 15 1 SCS1 MA 3 SCS1 MA 2 SCS1 MA 12 11 12 11 15 19 12 11 Rx 2 Rx 1 Tx 2 Tx 1 1 2 3 4 5 1 2 1 2 1 2 3 4 13 14 Rx 3 Tx 3 5 5 1 2 1 2 3 4 SCS1 MA 1 2 3 4 5 6 COM 11 12 13 14 15 16 17 18 19 20 PHOT F...

Page 46: ...46 LIBRA C MA D811494_07 ...

Page 47: ...LIBRA C MA 47 D811494_07 ...

Page 48: ......

Reviews: