The maximum output current is 0.5 A and the output stage is protected against overload.
Take possible limitation of the output current when connecting external devices (e.g.
increased surge current from lamps) into account.
Data of the the digital outputs
Feature
Value
Description
Output type
semiconductor
non-storing
Protective circuit for
inductive loads
41 V terminal voltage
(typ.) compared to
+24 V
fast de-excitation (must be provided
externally)
Status display
yes
one orange LED per output
Overload protection
yes
in the case of thermal overload
Short circuit
protection response
threshold
yes
electronic voltage limitation: typ. 7 A
The electricity is limited electronically.
Activation of short circuit protection results in
thermal overload and tripping of thermal
overload protection.
Permissible limits based on cold state: max.
10,000 short circuits; overall duration max.
500 hours.
Output delay “0”
after “1”
typ. 1 ms
–
Output delay “1”
after “0”
typ. 1 ms
–
Output capacity
< 20 nF
–
Rated voltage
+24 V DC
–
Voltage drop (at
rated current)
< 0.1 V
–
Rated current at “1”
signal
0.5 A
–
Total current of all
outputs
max. 2 A per group
group: 4 adjacent pins with supply from same
source (e.g. pins 1-4, power supply L1+)
Parallel circuit in two
outputs
max. 1 A
maximum permissible value with a logical
connection to increase performance