USER MANUAL 1.2 | B-FORTIS CC-PRIME SERIES
Berghof Automation GmbH | Arbachtalstrasse 26 | 72800 Eningen | www.berghof-automation.com
23
5.3.1. Digital outputs (O)
The digital outputs are positive switching 24 V outputs with an output current of max. 500 mA.
They have a common reference potential (GND) with the supply voltage. The supply lines are
organised into four groups of four.
The following counterpieces have been tested for the SC-SMT 3.81 (Weidmüller) plug-in
connector and are approved for use with the ECC22XX:
Weidmüller BCZ 3.81/16/180 (F, LH)
Weidmüller BCF 3.81/16/180 (F, LH)
Phoenix FK-MCP 1.5/16-ST-3.81-LR
Fig. 5: digital outputs plug X2 (Weidmüller SC-SMT 3.81/16/180 LF 3.2)
Digital outputs plug X2
Pin
Label
Assignment
1
2
3
4
O 1
O 2
O 3
O 4
+24 V (supply from L1+)
5
6
7
8
O 5
O 6
O 7
O 8
+24 V (supply from L2+)
9
10
11
12
O 9
O 10
O 11
O 12
+24 V (supply from L3+)
13
14
15
16
O 13
O 14
O 15
O 16
+24 V (supply from L4+)