8.3
Resetting a Fault
Faults can be reset in any one of four (4) ways:
A. Pressing the STOP key on the keypad.
B. Activating and then deactivating both the FWD and REV terminals simultaneously.
C. Removing and restoring AC power.
D. Using the automatic restart function
68-NRST
8.4
Fault Codes
FAULT
CAUSE
REMEDY
F01
Computer Malfunction
1. Reset the drive using the stop key for longer than 1 second.
0. If the problem persists, consult BERGES.
F02
Parameter Block Fault
1. Restore all parameters to factory settings by entering
81-PROG
= 1.
0. If the problem persists, consult BERGES.
F03
Bus Current Measurement
Fault
1. Reset the fault by pressing the stop key for longer than 1 second.
0. If the problem persists, consult BERGES.
F04
Power Supply Overload
1. Check for excessive loading on control terminals REF and V+ (see
F05
No DC Bus Voltage
1. Check for proper source voltage.
0. Check for DB component or output transistor failure.
0. Check for shorted DC bus.
F06
Output Short Circuit
1. Check motor wiring.
0. Reduce
52-BOOST
.
0. Extend
42-ACC1
accel. ramp.
F07
External Fault Mechanism
(i.e. Motor Overload Relay)
tripped
1. Check motor temperature.
0. Verify the sizing of MOL.
F09
Loss of Communication with
Control Terminal Strip
1. Reset the inverter using the stop key for longer than 1 second.
0. If the problem persists, consult BERGES.
F10
Auto-Restart (
68-NRST
)
number exceeded
1. Check the fault log (
07-FLT3
,
08-FLT2
, and
09-FLT1
).
0. Initiate corrective action for those faults.
NOTE:
RESETTING THIS FAULT MAY CAUSE INSTANT STARTING. EN-
SURE THAT DOING SO WILL NOT CAUSE HARM TO PERSONNEL
OR DAMAGE TO EQUIPMENT.
F11
Ground Fault
1. Check motor wiring.
0. Check for and remove any capacitive load.
F13
Overvoltage on DC Bus
1. Verify line voltage.
0. Check for excessive regenerative load.
0. Increase deceleration time.
0. Install perhaps optional external DB package.
F15
DB Overload
1. Reduce braking duty cycle.
0. Install optional external DB package.
0. Verify line voltage.
F16
Acceleration Overcurrent
1. Increase acceleration ramp time.
0. Check motor wiring for short circuit.
0. Check for “normal” operation with motor disconnected.