Ramp Differential Expansion Monitor Maintenance
84414-01
•
11
Test Alarms [Cont]
5. Adjust the power supply voltages such that the
differential expansion signal o n the monitor just
exceeds the Long Alert setpoint level and verify that
the Long ALERT LED goes on after the specified
delay period has elapsed (Flashing if the first out
option is selected).
6. Verify that the Alert relay changed state.
7. Press the RESET switch on the system monitor
and verify that the Long ALERT LED remains on
steady.
8. Adjust the power supply voltages such that the
differential expansion signal o n the monitor just
exceeds the Long Danger setpoint level and verify
that the Long DANGER LED goes o n after the
specified delay period has elapsed (Flashing if first
out option is selected).
9. Verify that the Danger relay changed state. The
relay will not change state if the Danger Bypass is
on.
z
DIFFERENTIAL
EXPANSION MONITOR
:d.
A • a r c
•
B
r u DANGER T. T 1 5
•
A L E P T
-
4 4 0 B Y P A S S 1 - 5 - J T
r Y, 5 E r,
• 1_ ER
B,FERED TPAr150LXITA5
F,CRENF ' L
2 0
•
Summary of Contents for 3300/46
Page 11: ...Ramp Differential Expansion Monitor Operation 8 4 4 1 3 0 1 Blank Page i v...
Page 13: ...Ramp Differential Expansion Monitor Operation 8 4 4 1 3 0 1 Blank Page v i...
Page 30: ...3300 46 RAMPDIFFERENTIAL EXPANSION MONITOR MAINTENANCE MANUAL BENTLY r NEVADA PART NO 84414 01...
Page 33: ...Ramp Differential Expansion Monitor Maintenance 84414 01 Blank Page i v...
Page 35: ...Ramp Differential Expansion Monitor Maintenance Blank Page 84414 01 v i...
Page 80: ...i w W2 19 E 1 Ramp Differential Expansion Monitor Schematic Sheet 6 of 11...
Page 82: ...f 99 9 L9 9 9 9 j T Ramp Differential Expansion Monitor Schematic Sheet 8 of 11...